Instruction Manual
Programming 7–31
Analog I/O
[Anlg Out 0 Sel] – Stand-Alone Version Only
[Anlg Out 1 Sel] – Stand-Alone Version Only
Thisparameterselects thesource valuethat willdrivethe
analog output. This output is intended for metering only
and should not be used as process control feedback.
Parameter Number 25, 274
Parameter Type Read and Write
Factory Default “Frequency” Out 0
“Current” Out 1
Units Display Drive Range
“Frequency” 0 Zerotoprogrammed[MaximumFreq]
“Current” 1 Zero to 200%
“Torque” 2 Zero to 200%
“Power” 3 Zero to 200%
“Voltage” 4 Zero to 200%
“% Motor OL” 5 Zero to 200%
“% Drive OL” 6 Zero to 200%
“Encoder” 7 See [Encoder Freq]
“Speed Error” 8 See [Speed Error]
“PI Reference” 9 See [PI Reference]
“PI Feedback” 10 See [PI Feedback]
“PI Error” 11 See [PI Error]
“PI Output” 12 See [PI Output]
[Anlg Out 0 Offst]
[Anlg Out 1 Offst]
Thisparameterenablesthevoltageorcurrentoffsetforthe
analog output. This internal value offsets 0-20mA to 4-
20mA and 0-10V to 2-10V.
Parameter Number 154, 278
Parameter Type Read and Write
Factory Default “Disabled”
Units Display Drive
“Disabled” 0
“Enabled” 1
[Anlg Out 0 Abs]
[Anlg Out 1 Abs]
Thisparameterselectswhetherasignedvalueorabsolute
value is used for analog out.
Parameter Number 233, 277
Parameter Type Read and Write
Factory Default “Enabled”
Units Display Drive
“Disabled” 0
“Enabled” 1
[Anlg Out 0 Lo]
[Anlg Out 1 Lo]
Sets the percentage of voltage or current output that rep-
resentsthe lowend ofthe “Range”listedin [AnlgOut Sel].
Parameter Number 234, 275
Parameter Type Read and Write
Display Units / Drive Units 0.1% / 4096 = 100%
Factory Default 0.0%
Minimum Value –300.0%
Maximum Value +300.0%
[Anlg Out 0 Hi]
[Anlg Out 1 Hi]
Sets the percentage of voltage or current output that rep-
resentsthehighendofthe“Range”listedin[AnlgOutSel].
Example: To get150% ofcurrent to equal10V/20mA, set
this parameter to 150%.
Parameter Number 235, 276
Parameter Type Read and Write
Display Units / Drive Units 0.1% / 4096 = 100%
Factory Default 100.0%
Minimum Value –300.0%
Maximum Value +300.0%
[Slot B Option] – Stand-Alone Version Only
[Slot A Option] – Stand-Alone Version Only
DisplaysthecatalognumberoftheanalogI/Ooptionboard
currently installed in slots A and/or B.
Parameter Number 252, 253
Parameter Type Read Only
Factory Default “Standard”
Units Display Drive
“Standard” 0
“LA1” 1
“LA2” 2
“LA3” 3
“LA4” 4
“LA5” 5
“LA6” 6
“LA7” 7
“Undefined” 8 Board not recognized