Manual

Startup
Chapter 9
9-5
Initial Operation Step 9b
- Motor Disconnected (cont.)
Speed select allows switching between one of two speed references. Is the
speed select function being used?
No Go to Step 9c.
Yes Close the speed select input. The display will show the speed
source programmed in Parameter 6. Parameter 6 may be one of the
following values.
Freq
P
R
Pr = - 0 if Parameter 6 = 0, Control Panel speed potentiometer.
Pr = - 1 if Parameter 6 = 1, 0-10V DC input.
Pr = - 2 if Parameter 6 = 2, 4-20mA input.
Pr = - 3 if Parameter 6 = 3, pulse train input.
Pr = - 4 if Parameter 6 = 4, serial input.
Pr = - 5 if Parameter 6 = 5, remote speed potentiometer input.
Check Parameter 84 – Analog Inverse.
If set to 1 (On), the 0-10V DC or 4-20mA input signals at Terminal Block
TB2 in the drive will produce an inverse speed signal.
A 0V DC or 4mA signal will produce maximum drive output frequency as
set by Parameter 19. A 10V DC or 20mA signal will produce minimum
drive output frequency as set by Parameter 16.