Specifications
Chapter 4
4-3
Input Power Voltage: 380-460V AC ±10%.
Frequency: 48 to 62Hz.
Phase: 3-phase.
AC Input Overvoltage Trip: 570V AC.
AC Input Undervoltage Trip: 275V AC.
Bus Overvoltage Trip: 810V DC
Bus Undervoltage Trip: 388V DC
Line Transient Protection: Line transients up to 5,000 volts peak, 320
Joules.
Logic Power Ride-Thru: 2 seconds or longer –– subject to the
integrity of user supplied external circuits.
Control Logic Noise: Showering arc transients from 350 to 2,000
Immunity volts peak.
Table
4.3  1336VT Input Current and kV
A
Input Power
Factor
Rating kVA In kVA In kVA In Displacement
Amps In Code 380V AC 415V AC 460V AC Angle kW/kVA
5.6 003 3.7 4.0 4.5 0.95 0.85
7.5 005 4.9 5.4 6.0 0.95 0.85
11.4 007 7.5 8.2 9.1 0.95 0.85
14.6 010 9.6 10.5 11.6 0.95 0.85
22.0 015 14.5 15.8 17.5 0.95 0.85
28.0 020 18.4 20.1 22.3 0.95 0.90
35.0 025 23.0 25.2 27.9 0.95 0.90
44.0 030 29.0 31.6 35.1 0.95 0.90
54.0 040 35.5 38.8 43.0 0.95 0.90
67.0 050 44.1 48.2 53.4 0.95 0.90
78.0 060 51.3 56.1 62.1 0.95 0.90
97.0 075 63.8 69.7 77.3 0.95 0.90
124.0 100 81.6 89.1 98.8 0.95 0.90
154.0 125 101.4 110.7 122.7 0.95 0.90
178.0 150 117.2 127.9 141.8 0.95 0.90
235.0 200 154.7 168.9 187.2 0.95 0.90
296.0 250 194.8 212.8 235.8 0.95 0.90