Appendix A Motor Cable Length Restrictions Tables
Table 29 - PowerFlex 700 (standard/vector) Drives, 690V Shielded/Unshielded Cable – Meters (Feet)
PowerFlex 700H
This section lists motor cable length restrictions, reactors, and available options
for PowerFlex 700H drives.
Table 30 - PowerFlex 700H Drives, 400V Shielded/Unshielded Cable – Meters (Feet)
Drive No Solution Reactor Only Reactor and Damping Resistor Reactor Resistor Available Options
Frame kW kHz 1850V 2000V 1850V 2000V 1850V 2000V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
4
45
2 30.5 (100) 106.7 (350) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R80-C 50 345
4 24.4 (80) 76.2 (250) 36.6 (120) 121.9 (400) 213.4 (700) 274.3 (900) 1321-3R80-C 50 690
55
2 30.5 (100) 106.7 (350) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R80-C 50 345
4 24.4 (80) 76.2 (250) 36.6 (120) 106.7 (350) 213.4 (700) 274.3 (900) 1321-3R80-C 50 690
5
75
2 30.5 (100) 106.7 (350) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R100-C 50 345
4 30.5 (100) 76.2 (250) 36.6 (120) 106.7 (350) 213.4 (700) 274.3 (900) 1321-3R100-C 50 690
90
2 30.5 (100) 106.7 (350) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R130-C 50 375
4 30.5 (100) 76.2 (250) 36.6 (120) 106.7 (350) 182.9 (600) 274.3 (900) 1321-3R130-C 50 750
6
110
2 30.5 (100) 106.7 (350) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R160-C 50 375
4 30.5 (100) 76.2 (250) 36.6 (120) 99.1 (325) 152.4 (500) 274.3 (900) 1321-3R160-C 50 750
132
2 30.5 (100) 106.7 (350) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R200-C 50 375
4 30.5 (100) 76.2 (250) 36.6 (120) 83.8 (275) 152.4 (500) 274.3 (900) 1321-3R200-C 50 750
Drive No Solution Reactor Only Reactor and Damping Resistor
or 1321-RWR
Reactor/RWR
(see page 129
)
Resistor Available Options
Frame kW kHz 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
9
132 2
24.4
(80)
48.8
(160)
76.2
(250)
137.2
(450)
24.4
(80)
48.8
(160)
365.8
(1200)
365.8
(1200)
121.9
(400)
274.3
(900)
365.8
(1200)
365.8
(1200)
1321-RWR320-DP
●
160 2
24.4
(80)
48.8
(160)
76.2
(250)
137.2
(450)
24.4
(80)
48.8
(160)
365.8
(1200)
365.8
(1200)
121.9
(400)
274.3
(900)
365.8
(1200)
365.8
(1200)
1321-RWR320-DP
●
10
200 2
24.4
(80)
48.8
(160)
76.2
(250)
121.9
(400)
24.4
(80)
48.8
(160)
365.8
(1200)
365.8
(1200)
121.9
(400)
274.3
(900)
365.8
(1200)
365.8
(1200)
1321-3R500-B 20 495
(3)
(3) Resistor specification is based on two cables per phase.
●
250 2
24.4
(80)
48.8
(160)
61.0
(200)
121.9
(400)
24.4
(80)
48.8
(160)
365.8
(1200)
365.8
(1200)
121.9
(400)
274.3
(900)
365.8
(1200)
365.8
(1200)
1321-3R500-B 20 495
(3)
●
11
315 2
18.3
(60)
42.7
(140)
61.0
(200)
121.9
(400)
18.3
(60)
42.7
(140)
365.8
(1200)
365.8
(1200)
121.9
(400)
243.8
(800)
365.8
(1200)
365.8
(1200)
1321-3R600-B 20 495
(3)
●
355 2
18.3
(60)
42.7
(140)
61.0
(200)
121.9
(400)
18.3
(60)
42.7
(140)
304.8
(1000)
365.8
(1200)
121.9
(400)
243.8
(800)
365.8
(1200)
365.8
(1200)
1321-3R750-B 20 495
(3)
●
400 2
18.3
(60)
42.7
(140)
61.0
(200)
121.9
(400)
18.3
(60)
42.7
(140)
274.3
(900)
365.8
(1200)
121.9
(400)
243.8
(800)
365.8
(1200)
365.8
(1200)
1321-3R750-B 20 735
(4)
(4) Resistor specification is based on three cables per phase.
●
12
(1)
(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.
450 2
18.3
(60)
42.7
(140)
61.0
(200)
121.9
(400)
18.3
(60)
42.7
(140)
243.8
(800)
365.8
(1200)
121.9
(400)
243.8
(800)
365.8
(1200)
365.8
(1200)
2 x
1321-3RB400-B
40 375
(4)
●
500 2
12.2
(40)
42.7
(140)
61.0
(200)
121.9
(400)
18.3
(60)
42.7
(140)
243.8
(800)
365.8
(1200)
121.9
(400)
243.8
(800)
365.8
(1200)
365.8
(1200)
2 x
1321-3R500-B
40 375
(4)
●
560 2
12.2
(40)
42.7
(140)
61.0
(200)
121.9
(400)
18.3
(60)
42.7
(140)
243.8
(800)
365.8
(1200)
121.9
(400)
243.8
(800)
365.8
(1200)
365.8
(1200)
2 x
1321-3R500-B
20 525
(5)
(5) Resistor specification is based on four cables per phase.
13
630
(2)
(2) Some Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.
2
12.2
(40)
61.0
(200)
99.1
(325)
167.6
(550)
36.6
(120)
61.0
(200)
304.8
(1000)
365.8
(1200)
198.1
(650)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R600-B
20 525
(5)
710
(2)
2
12.2
(40)
61.0
(200)
99.1
(325)
167.6
(550)
36.6
(120)
61.0
(200)
304.8
(1000)
365.8
(1200)
198.1
(650)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R750-B
20 525
(5)
800
(2)
2
12.2
(40)
61.0
(200)
99.1
(325)
167.6
(550)
36.6
(120)
61.0
(200)
304.8
(1000)
365.8
(1200)
198.1
(650)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R750-B
20 525
(5)