Manual
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014 87
Motor Cable Length Restrictions Tables Appendix A
Table 20 - PowerFlex 40 Drives, 600V Shielded/Unshielded Cable – Meters (Feet)
Rating No Solution Reactor Only Reactor and
Damping Resistor
or 1321-RWR
Reactor/RWR
(see page 129
)
Resistor Available Options
Hp kHz 1488V 1850V 1488V 1600V 1488V 1600V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
12/4
42.7
(140)
121.9
(400)
121.9
(400)
121.9
(400)
121.9
(400)
121.9
(400)
●●●
22/4
42.7
(140)
152.4
(500)
152.4
(500)
152.4
(500)
152.4
(500)
152.4
(500)
●●●
32/4
42.7
(140)
152.4
(500)
152.4
(500)
152.4
(500)
182.9
(600)
182.9
(600)
●●●
52/4
42.7
(140)
152.4
(500)
152.4
(500)
243.8
(800)
243.8
(800)
243.8
(800)
1321-RWR8-DP
●●●●
7.5 2/4
42.7
(140)
182.9
(600)
152.4
(500)
304.8
(1000)
304.8
(1000)
304.8
(1000)
1321-RWR12-DP
●●
10 2/4
42.7
(140)
182.9
(600)
152.4
(500)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR18-DP
●●
15 2/4
42.7
(140)
182.9
(600)
152.4
(500)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR25-DP
●