Best Practices
This chapter discusses various installation practices.
Mounting
Standard Installations
There are many criteria in determining the appropriate enclosure. Some of these
include:
Environment
EMC compatibility/compliance
Available space
Access/Wiring
Safety guidelines
Grounding to the Component Mounting Panel
In the example below, the drive chassis ground plane is extended to the mounting
panel. The panel is made of zinc-plated steel that helps to create a proper bond
between chassis and panel.
Figure 20 - Drive Chassis Ground Plane Extended to the Panel
IMPORTANT
Where TE and PE terminals are provided, ground each separately to the nearest
point on the panel with flat braid.
Drive Ground Plane (chassis)