Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014 47
Power Distribution Chapter 2
DC Bus Connections
For reliable system operation, minimize the interconnection of drives to the DC
bus and the inductance levels between the drives. Use a low inductance-type DC
bus (for example, 0.35 μH/m or less).
Figure 13 - Star Configuration of Common Bus Connections
Bus Bar Versus Cable
Follow these recommendations for using a bus bar versus a cable:
A DC bus bar is recommended versus a cable.
When a DC bus bar cannot be used, follow these guidelines for DC bus
cables:
Use twisted cable where possible, approximately one twist per inch.
Use cable rated for the equivalent AC voltage rating. The peak AC
voltage is equivalent to the DC voltage. For example, the peak AC
voltage on a 480V AC system no load is 480 x 1.414 = 679V peak. The
679V peak corresponds to 679V DC at no load.
IMPORTANT
Do not daisy chain the DC bus connections. Configure the DC bus connections in
a star configuration to allow for proper fusing.