Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014 43
Power Distribution Chapter 2
Multi-drive Protection
Use a separate line reactor for each drive that shares a common power line.
Individual line reactors provide filtering between each drive to provide optimum
surge protection for each drive. However, if it is necessary to group more than one
drive on a single AC line reactor, use this process to verify that the AC line
reactor provides a minimum amount of impedance:
• In general, up to five drives can be grouped on one reactor.
• Add the input currents of the drives in the group.
• Multiply that sum by 125%.
• Refer to 1321 Power Conditioning Products Technical Data, publication
1321-TD001
, to select a reactor with a maximum continuous current
rating greater than the multiplied current.
1336 PLUS,
PLUS II
IMPACT
FORCE
C250 600 187 (250) 2500 3R250-B 0.09 250
C300 600 224 (300) 3000 3R320-B 0.075 320
C350 600 261 (350) 3000 3R400-B 0.06 400
C400 600 298 (400) 4000 3R400-B 0.06 400
C450 600 336 (450) 4500 3R500-B 0.05 500
C500 600 373 (500) 5000 3R500-B 0.05 500
C600 600 448 (600) 5000 3R600-B 0.04 600
C650 600 (650) 5000 3R750-B 0.029 750
C700 600 (700) 5000 3R850-B FN-1 0.027 850
C800 600 (800) 5000 3R850-B FN-1 0.027 850
CP/CPR350 600 261 (350) N/A N/A N/A N/A
CP/CPR400 600 298 (400) N/A N/A N/A N/A
(1) Shaded rows identify drive ratings without built-in inductors.
(2) Maximum suggested KVA supply without consideration for additional inductance.
(3) 2000 KVA represents 2 MVA and greater.
(4) N/A = not available at time of printing.
Table 13 - AC Line Impedance Recommendations for Bulletin 1336 Drives (Continued)
Drive
Drive Catalog
Number
(1)
Volts kW (Hp) Max Supply
kVA
(2)(3)
3% Line Reactor
Open Style, 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
(4)