Manual
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014 37
Power Distribution Chapter 2
PowerFlex
700/700S
For
PowerFlex
700S,
replace 20B
with 20D.
20BD1P1 480 0.37 (0.5) 250 3R2-B 20 2
20BD2P1 480 0.75 (1) 250 3R2-B 20 2
20BD3P4 480 1.5 (2) 500 3R4-B 6.5 4
20BD5P0 480 2.2 (3) 500 3R4-B 6.5 4
20BD8P0 480 4.0 (5) 500 3R8-B 3 8
20BD011 480 5.5 (7.5) 750 3R12-B 2.5 12
20BD014 480 7.5 (10) 750 3R18-B 1.5 18
20BD022 480 11 (15) 750 3R25-B 1.2 25
20BD027 480 15 (20) 750 3R35-B 0.8 35
20BD034 480 18.5 (25) 1000 3R35-B 0.8 35
20BD040 480 22 (30) 1000 3R45-B 0.7 45
20BD052 480 30 (40) 1000 3R55-B 0.5 55
20BD065 480 37 (50) 1000 3R80-B 0.4 80
20BD077 480 45 (60) 1000 3R80-B 0.4 80
20BD096 480 55 (75) 1000 3R100-B 0.3 100
20BD125 480 75 (100) 1000 3R130-B 0.2 130
20BD140 480 75 (100) 1000 3R160-B 0.15 160
20BD156 480 90 (125) 1500 3R160-B 0.15 160
20BD180 480 110 (150) 1500 3R200-B 0.11 200
20BE0P9 600 0.37 (0.5) 250 3R2-B 20 2
20BE1P7 600 0.75 (1) 250 3R2-B 20 2
20BE2P7 600 1.5 (2) 500 3R4-B 6.5 4
20BE3P9 600 2.2 (3) 500 3R4-B 6.5 4
20BE6P1 600 4.0 (5) 500 3R8-B 3 8
20BE9P0 600 5.5 (7.5) 750 3R8-B 3 8
20BE011 600 7.5 (10) 750 3R12-B 2.5 12
20BE017 600 11 (15) 750 3R25-B 1.2 25
20BE022 600 15 (20) 750 3R25-B 1.2 25
20BE027 600 18.5 (25) 1000 3R35-B 0.8 35
20BE032 600 22 (30) 1000 3R35-B 0.8 35
20BE041 600 30 (40) 1000 3R45-B 0.7 45
20BE052 600 37 (50) 1000 3R55-B 0.5 55
20BE062 600 45 (60) 1000 3R80-B 0.4 80
20BE077 600 55 (75) 1000 3R80-B 0.4 80
20BE099 600 75 (100) 1200 3R100-B 0.3 100
20BE125 600 90 (125) 1400 3R130-B 0.2 130
20BE144 600 110 (150) 1500 3R160-B 0.15 160
(1) Maximum suggested KVA supply without consideration for additional inductance
Table 11 - AC Line Impedance Recommendations for PowerFlex 700/700S Drives (Continued)
Drive Drive Catalog
Number
Volts kW (Hp) Max Supply
KVA
(1)
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)