Manual

36 Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Chapter 2 Power Distribution
PowerFlex
70
20AE031 600 22 (30) 1000 3R35-B 0.8 35
20AE042 600 30 (40) 1000 3R45-B 0.7 45
20AE051 600 37 (50) 1000 3R55-B 0.5 55
(1) Shaded rows identify drive ratings without built-in inductors.
(2) Maximum suggested KVA supply without consideration for additional inductance.
(3) N/A = not available at time of printing.
Table 11 - AC Line Impedance Recommendations for PowerFlex 700/700S Drives
Drive Drive Catalog
Number
Volts kW (Hp) Max Supply
KVA
(1)
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
PowerFlex
700/700S
For
PowerFlex
700S,
replace 20B
with 20D.
20BB2P2 240 0.37 (0.5) 100 3R2-D 6 2
20BB4P2 240 0.75 (1) 125 3R4-A 3 4
20BB6P8 240 1.5 (2) 200 3R8-A 1.5 8
20BB9P6 240 2.2 (3) 300 3R12-A 1.25 12
20BB015 240 3.7 (5) 400 3R18-A 0.8 18
20BB022 240 5.5 (7.5) 500 3R25-A 0.5 25
20BB028 240 7.5 (10) 750 3R35-A 0.4 35
20BB042 240 11 (15) 1000 3R45-A 0.3 45
20BB052 240 15 (20) 1000 3R80-A 0.2 80
20BB070 240 18.5 (25) 1000 3R80-A 0.2 80
20BB080 240 22 (30) 1000 3R100-A 0.15 100
20BB104 240 30 (40) 1000 3R130-A 0.1 130
20BB130 240 37 (50) 1000 3R130-A 0.1 130
20BB154 240 45 (60) 1000 3R160-A 0.075 160
20BB192 240 55 (75) 1000 3R200-A 0.055 200
20BB260 240 75 (100) 1000 3R320-A 0.04 320
20BC1P3 400 0.37 (5) 250 3R2-B 20 2
20BC2P1 400 0.75 (1) 250 3R2-B 20 2
20BC3P5 400 1.5(2) 500 3R4-B 6.5 4
20BC5P0 400 2.2 (3) 500 3R4-B 6.5 4
20BC8P7 400 4 (5) 500 3R8-B 3 8
20BC011 400 5.5 (7.5) 750 3R12-B 2.5 12
20BC015 400 7.5 (10) 1000 3R18-B 1.5 18
20BC022 400 11 (15) 1000 3R25-B 1.2 25
20BC030 400 15 (20) 1000 3R35-B 0.8 35
20BC037 400 18.5(25) 1000 3R45-B 0.7 45
20BC043 400 22 (30) 1000 3R45-B 0.7 45
20BC056 400 30 (40) 1000 3R55-B 0.5 55
20BC072 400 37 (50) 1000 3R80-B 0.4 80
20BC085 400 45 (60) 1000 3R130-B 0.2 130
20BC105 400 55 (75) 1000 3R130-B 0.2 130
20BC125 400 55 (75) 1000 3R130-B 0.2 130
20BC140 400 75 (100) 1000 3R160-B 0.15 160
20BC170 400 90 (125) 1500 3R200-B 0.11 200
20BC205 400 110 (150) 1500 3R200-B 0.11 200
20BC260 400 132 (175) 2000 3RB320-B 0.075 320
continued
Table 10 - AC Line Impedance Recommendations for PowerFlex 70 Drives (Continued)
Drive Drive Catalog
Number
(1)
Volts kW (Hp) Max Supply
kVA
(2)
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
(3)