Manual
34 Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Chapter 2 Power Distribution
Table 9 - AC Line Impedance Recommendations for PowerFlex 525 Drives
Drive Drive Catalog
Number
(1)
(1) Shaded rows identify drive ratings without built-in inductors.
Volts kW (Hp) Max Supply
kVA
(2)
(2) Maximum suggested KVA supply without consideration for additional inductance.
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
PowerFlex
525
25BB2P5 240 0.4 (0.5) 25 3R4-B 6.5 4
25BB5P0 240 0.75 (1.0) 50 3R8-B 3 8
25BB8P0 240 1.5 (2.0) 50 3R8-A 1.5 8
25BB012 240 2.2 (3.0) 50 3R12-A 1.25 12
25BB017 240 3.7 (5.0) 50 3R18-A 0.8 18
25BB024 240 5.5 (7.5) 100 3R25-A 0.5 25
25BB032 240 7.5 (10.0) 150 3R35-A 0.4 35
25BB048 240 11.0 (15.0) 150 3R55-B 0.5 55
25BB062 240 7.5 (10.0) 150 3R80-B 0.4 80
25BD1P4 480 0.4 (0.5) 15 3R2-B 20 2
25BD2P3 480 0.75 (1.0) 30 3R4-C 9 4
25BD4P0 480 1.5 (2.0) 50 3R4-B 6.5 4
25BD6P0 480 2.2 (3.0) 75 3R8-C 5 8
25BD010 480 3.7 (5.0) 100 3R8-B 3 8
25BD013 480 5.5 (7.5) 120 3R12-B 2.5 12
25BD017 480 7.5 (10.0) 150 3R18-B 1.5 18
25BD024 480 11.0 (15.0) 200 3R25-B 1.2 25
25BD030 480 15.0 (20.0) 200 3R35-B 0.8 35
25BD037 480 18.5 (25.0) 500 3R45-B 0.7 45
25BD043 480 22 (30.0) 500 3R45-B 0.7 45
25BE0P9 600 0.40(0.5) 20 3R2-B 20 2
25BE1P7 600 0.75 (1.0) 20 3R2-B 20 2
25BE3P0 600 1.5 (2.0) 30 3R4-B 6.5 4
25BE4P2 600 2.2 (3.0) 50 3R4-B 6.5 4
25BE6P6 600 3.7 (5.0) 75 3R8-C 5 8
25BE9P9 600 5.5 (7.5) 120 3R12-B 2.5 12
25BE012 600 7.5 (10.0) 150 3R12-B 2.5 12
25BE019 600 11.0 (15.0) 200 3R18-B 1.5 18
25BE022 600 15.0 (20.0) 200 3R25-B 1.2 25
25BE027 600 18.5 (25.0) 500 3R35-B 0.8 35
25BE032 600 22 (30.0) 500 3R35-B 0.8 35