Manual

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014 33
Power Distribution Chapter 2
Table 8 - AC Line Impedance Recommendations for PowerFlex 400 Drives
Drive Drive Catalog
Number
(1)
(1) Shaded rows identify drive ratings without built-in inductors.
Volts kW (Hp) Max Supply
kVA
(2)
(2) Maximum suggested KVA supply without consideration for additional inductance.
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
PowerFlex
400
22CB012 240 2.2 (3.0) 50 3R12-A N/A N/A
22CB017 240 3.7 (5.0) 50 3R18-A N/A N/A
22CB024 240 5.5 (7.5) 200 3R25-A 0.5 25
22CB033 240 7.7 (10.0) 275 3R35-A 0.4 35
22CB049 240 11 (15.0) 350 3R45-A 0.3 45
22CB065 240 15 (20.0) 425 3R55-A 0.25 55
22CB075 240 18.5 (25.0) 550 3R80-A 0.2 80
22CB090 240 22 (30.0) 600 3R100-A 0.15 100
22CB120 240 30 (40.0) 750 3R130-A 0.1 130
22CB145 240 37 (50.0) 800 3R160-A 0.075 160
22CD6P0 480 2.2 (3.0) N/A N/A N/A N/A
22CD010 480 3.7 (5.0) N/A N/A N/A N/A
22CD012 480 5.5 (7.5) N/A N/A N/A N/A
22CD017 480 7.5 (10) N/A N/A N/A N/A
22CD022 480 11 (15) N/A N/A N/A N/A
22CD030 480 15 (20) N/A N/A N/A N/A
22CD038 480 18.5 (25) N/A N/A N/A N/A
22CD045 480 22 (30) N/A N/A N/A N/A
22CD060 480 30 (40) N/A N/A N/A N/A
22CD072 480 37 (50) N/A N/A N/A N/A
22CD088 480 45 (60) N/A N/A N/A N/A
22CD105 480 55 (75) N/A N/A N/A N/A
22CD142 480 75 (100) N/A N/A N/A N/A
22CD170 480 90 (125) N/A N/A N/A N/A
22CD208 480 110 (150) N/A N/A N/A N/A