32 Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Chapter 2 Power Distribution
Table 7 - AC Line Impedance Recommendations for PowerFlex 40 Drives
Drive Drive Catalog
Number
(1)
(1) Shaded rows identify drive ratings without built-in inductors.
Volts kW (Hp) Max Supply
kVA
(2)
(2) Maximum suggested KVA supply without consideration for additional inductance.
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
PowerFlex
40
22BB2P3 240 0.4 (0.5) 25 3R4-B 6.5 4
22BB5P0 240 0.75 (1.0) 50 3R8-B 3 8
22BB8P0 240 1.5 (2.0) 50 3R8-A 1.5 8
22BB012 240 2.2 (3.0) 50 3R12-A 1.25 12
22BB017 240 3.7 (5.0) 50 3R18-A 0.8 18
22BB024 240 5.5 (7.5) 100 3R25-A 0.5 25
22BB033 240 7.5 (10.0) 150 3R35-A 0.4 35
22BD1P4 480 0.4 (0.5) 15 3R2-B 20 2
22BD2P3 480 0.75 (1.0) 30 3R4-C 9 4
22BD4P0 480 1.5 (2.0) 50 3R4-B 6.5 4
22BD6P0 480 2.2 (3.0) 75 3R8-C 5 8
22BD010 480 3.7 (5.0) 100 3R8-B 3 8
22BD012 480 5.5 (7.5) 120 3R12-B 2.5 12
22BD017 480 7.5 (10.0) 150 3R18-B 1.5 18
22BD024 480 11.0 (15.0) 200 3R25-B 1.2 25
22BE1P7 600 0.75 (1.0) 20 3R2-B 20 2
22BE3P0 600 1.5 (2.0) 30 3R4-B 6.5 4
22BE4P2 600 2.2 (3.0) 50 3R4-B 6.5 4
22BE6P6 600 3.7 (5.0) 75 3R8-C 5 8
22BE9P9 600 5.5 (7.5) 120 3R12-B 2.5 12
22BE012 600 7.5 (10.0) 150 3R12-B 2.5 12
22BE019 600 11.0 (15.0) 200 3R18-B 1.5 18