128 Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Appendix A Motor Cable Length Restrictions Tables
160 Drives
This section lists motor cable data for 160 drives.
Table 58 - 160 Drives, 480V – Meters (Feet)
Table 59 - 160 Drive, 240V and 480V – Cable Charging Current – Meters (Feet)
380…460V
Ratings
Motor Insulation Rating -
VoltsP-P
Motor Cable Only RWR at Drive Reactor at Motor
Shielded Unshielded Shielded Unshielded Shielded Unshielded
4.0 kW
(5 Hp)
1000 13.7 (45) 6.1 (20) 160.0 (525) 182.9 (600) 99.1 (325) 91.4 (300)
1200 27.4 (90) 12.2 (40) 160.0 (525) 182.9 (600) 160.0 (525) 129.5 (425)
1600 160.0 (525) 144.8 (475) 160.0 (525) 182.9 (600) 160.0 (525) 182.9 (600)
2.2 kW
(3 Hp)
1000 12.2 (40) 12.2 (40) 160.0 (525) 182.9 (600) 68.6 (225) 76.2 (250)
1200 27.4 (90) 18.3 (60) 160.0 (525) 182.9 (600) 99.1 (325) 129.5 (425)
1600 160.0 (525) 152.4 (500) 160.0 (525) 182.9 (600) 160.0 (525) 182.9 (600)
1.5 kW
(2 Hp)
1000 12.2 (40) 12.2 (40) 129.5 (425) 182.9 (600) 99.1 (325) 91.4 (300)
1200 27.4 (90) 18.3 (60) 129.5 (425) 182.9 (600) 129.5 (425) 137.2 (450)
1600 152.4 (500) 152.4 (500) 129.5 (425) 182.9 (600) 164.6 (540) 182.9 (600)
0.75 kW
(1 Hp)
1000 16.8 (55) 12.2 (40) 99.1 (325) 182.9 (600) 99.1 (325) 106.7 (350)
1200 38.1 (125) 18.3 (60) 99.1 (325) 182.9 (600) 152.4 (500) 137.2 (450)
1600 152.4 (500) 152.4 (500) 99.1 (325) 182.9 (600) 152.4 (500) 182.9 (600)
0.55 kW
(0.75 Hp)
1000 13.7 (45) 12.2 (40) 91.4 (300) 182.9 (600) 91.4 (300) 91.4 (300)
1200 38.1 (125) 18.3 (60) 91.4 (300) 182.9 (600) 152.4 (500) 152.4 (500)
1600 152.4 (500) 152.4 (500) 91.4 (300) 182.9 (600) 152.4 (500) 182.9 (600)
0.37 kW
(0.5 Hp)
1000 13.7 (45) 27.4 (90) 91.4 (300) 129.5 (425) 91.4 (300) 129.5 (425)
1200 38.1 (125) 54.9 (180) 91.4 (300) 129.5 (425) 152.4 (500) 152.4 (500)
1600 152.4 (500) 152.4 (500) 91.4 (300) 129.5 (425) 152.4 (500) 152.4 (500)
480V
Ratings
kHz Motor Cable Only RWR at Drive (NR = not recommended) Reactor at Motor
Shielded
(1)
(1) When you use shielded cable at lightly loaded conditions, cable length recommendations for drives rated 0.75 kW (1 Hp) and below are 61 m (200 ft).
Unshielded Shielded
(1)
Unshielded Shielded
(1)
Unshielded
4.0 kW
(5 Hp)
2 106.7 (350) 182.9 (600) 91.4 (300) 182.9 (600) 121.9 (400) 182.9 (600)
4 129.5 (425) 182.9 (600) 106.7 (350) 182.9 (600) 137.2 (450) 182.9 (600)
8 144.8 (475) 152.4 (500) NR NR 137.2 (450) 152.4 (500)
2.2 kW
(3 Hp)
2 109.7 (360) 182.9 (600) 85.3 (280) 182.9 (600) 121.9 (400) 182.9 (600)
4 114.3 (375) 182.9 (600) 83.8 (275) 182.9 (600) 121.9 (400) 182.9 (600)
8 121.9 (400) 152.4 (500) NR NR 121.9 (400) 152.4 (500)
1.5 kW
(2 Hp)
2 91.4 (300) 167.6 (550) 83.8 (275) 182.9 (600) 91.4 (300) 182.9 (600)
4 91.4 (300) 167.6 (550) 83.8 (275) 182.9 (600) 91.4 (300) 152.4 (500)
8 99.1 (325) 152.4 (500) NR NR 106.7 (350) 152.4 (500)
0.75 kW
(1 Hp)
2 61.0 (200) 114.3 (375) 61.0 (200) 129.5 (425) 68.6 (225) 121.9 (400)
4 68.6 (225) 114.3 (375) 61.0 (200) 129.5 (425) 68.6 (225) 114.3 (375)
8 76.2 (250) 114.3 (375) NR NR 68.6 (225) 121.9 (400)
0.55 kW
(0.75 Hp)
2 54.9 (180) 106.7 (350) 54.9 (180) 114.3 (375) 54.9 (180) 106.7 (350)
4 54.9 (180) 106.7 (350) 54.9 (180) 114.3 (375) 54.9 (180) 106.7 (350)
8 54.9 (180) 106.7 (350) NR NR 54.9 (180) 106.7 (350)
0.37 kW
(0.5 Hp)
2 30.5 (100) 99.1 (325) 30.5 (100) 106.7 (350) 30.5 (100) 91.4 (300)
4 30.5 (100) 99.1 (325) 30.5 (100) 106.7 (350) 30.5 (100) 106.7 (350)
8 30.5 (100) 99.1 (325) NR 30.5 (100) 106.7 (350)
240V Ratings No Reactor RWR at Drive Reactor at Motor
0.37 to 4.0 kW
(0.5 to 5 Hp)
2 through 8 kHz
Shielded
(1)
Unshielded Shielded
(1)
Unshielded Shielded
(1)
Unshielded
160.0 (525) 182.9 (600) NR NR 160.0 (525) 182.9 (600)