Manual

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014 119
Motor Cable Length Restrictions Tables Appendix A
9
(1)
500
2
24.4
(80)
76.2
(250)
152.4
(500)
213.4
(700)
61.0
(200)
152.4
(500)
304.8
(1000)
365.8
(1200)
213.4
(700)
304.8
(1000)
365.8
(1200)
365.8
(1200)
2 x
1321-3R500-B
40 375
(3)
4
24.4
(80)
61.0
(200)
106.7
(350)
137.2
(450)
36.6
(120)
91.4
(300)
182.9
(600)
274.3
(900)
91.4
(300)
182.9
(600)
365.8
(1200)
365.8
(1200)
40 750
(3)
560
2
24.4
(80)
61.0
(200)
152.4
(500)
182.9
(600)
61.0
(200)
152.4
(500)
304.8
(1000)
365.8
(1200)
182.9
(600)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R600-B
20 525
(4)
4
24.4
(80)
61.0
(200)
106.7
(350)
137.2
(450)
36.6
(120)
91.4
(300)
182.9
(600)
274.3
(900)
91.4
(300)
182.9
(600)
365.8
(1200)
365.8
(1200)
20 1050
(4)
630
2
24.4
(80)
61.0
(200)
152.4
(500)
182.9
(600)
61.0
(200)
152.4
(500)
304.8
(1000)
365.8
(1200)
182.9
(600)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R600-B
20 525
(4)
4
24.4
(80)
61.0
(200)
106.7
(350)
137.2
(450)
36.6
(120)
91.4
(300)
182.9
(600)
274.3
(900)
91.4
(300)
182.9
(600)
365.8
(1200)
365.8
(1200)
20 1050
(4)
710
2
24.4
(80)
61.0
(200)
152.4
(500)
182.9
(600)
61.0
(200)
152.4
(500)
304.8
(1000)
365.8
(1200)
182.9
(600)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R600-B
20 525
(4)
4
24.4
(80)
61.0
(200)
106.7
(350)
137.2
(450)
36.6
(120)
91.4
(300)
182.9
(600)
274.3
(900)
91.4
(300)
182.9
(600)
365.8
(1200)
365.8
(1200)
20 1050
(4)
800
2
24.4
(80)
61.0
(200)
152.4
(500)
182.9
(600)
61.0
(200)
152.4
(500)
304.8
(1000)
365.8
(1200)
182.9
(600)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R750-B
20 525
(4)
4
24.4
(80)
61.0
(200)
106.7
(350)
137.2
(450)
36.6
(120)
91.4
(300)
182.9
(600)
274.3
(900)
91.4
(300)
182.9
(600)
365.8
(1200)
365.8
(1200)
20 1050
(4)
850
2
24.4
(80)
61.0
(200)
152.4
(500)
182.9
(600)
61.0
(200)
152.4
(500)
304.8
(1000)
365.8
(1200)
182.9
(600)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R750-B
20 525
(4)
4
24.4
(80)
61.0
(200)
106.7
(350)
137.2
(450)
36.6
(120)
91.4
(300)
182.9
(600)
274.3
(900)
91.4
(300)
182.9
(600)
365.8
(1200)
365.8
(1200)
20 1050
(4)
10
(1)
900
2
24.4
(80)
45.7
(150)
121.9
(400)
182.9
(600)
61.0
(200)
152.4
(500)
304.8
(1000)
365.8
(1200)
182.9
(600)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R850-B
20 600
(5)
4
24.4
(80)
45.7
(150)
91.4
(300)
137.2
(450)
36.6
(120)
91.4
(300)
182.9
(600)
274.3
(900)
91.4
(300)
182.9
(600)
365.8
(1200)
365.8
(1200)
20 1200
(5)
1250
2
24.4
(80)
45.7
(150)
106.7
(350)
152.4
(500)
61.0
(200)
121.9
(400)
304.8
(1000)
365.8
(1200)
152.4
(500)
274.3
(900)
365.8
(1200)
365.8
(1200)
3 x
1321-3R750-B
30 500
(6)
4
24.4
(80)
45.7
(150)
76.2
(250)
121.9
(400)
36.6
(120)
91.4
(300)
152.4
(500)
213.4
(700)
91.4
(300)
182.9
(600)
365.8
(1200)
365.8
(1200)
30 1000
(6)
(1) Frame 9 and Frame 10 drives require two or three parallel reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.
(2) Resistor specification is based on two parallel cables per phase.
(3) Resistor specification is based on three parallel cables per phase.
(4) Resistor specification is based on four parallel cables per phase.
(5) Resistor specification is based on five parallel cables per phase.
(6) Resistor specification is based on six parallel cables per phase.
Table 50 - PowerFlex 755 Floor Mount Drives, 400V Shielded/Unshielded Cable – Meters (Feet) (continued)
Drive Rating No Solution Reactor Only Reactor and Damping Resistor Reactor Resistor Available Options
Frame kW kHz 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC