Manual

108 Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Appendix A Motor Cable Length Restrictions Tables
Table 45 - PowerFlex 700S Drives, 690V Shielded/Unshielded Cable – Meters (Feet)
Drive No Solution Reactor Only Reactor and Damping
Resistor
Reactor Resistor Available Options
Frame kW kHz 1850V 2000V 1850V 2000V 1850V 2000V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
5
45 2/4 24.4 (80) 45.7 (150) 61.0 (200) 106.7 (350) 365.8 (1200) 365.8 (1200) 1321-3R80-C 50 375/750
55 2/4 24.4 (80) 45.7 (150) 61.0 (200) 106.7 (350) 365.8 (1200) 365.8 (1200) 1321-3R80-C 50 375/750
75 2/4 24.4 (80) 45.7 (150) 61.0 (200) 106.7 (350) 365.8 (1200) 365.8 (1200) 1321-3R100-C 50 375/750
90 2/4 24.4 (80) 45.7 (150) 61.0 (200) 106.7 (350) 243.8 (800) 274.3 (900) 1321-3R130-C 50 375/750
6
110 2/4 24.4 (80) 45.7 (150) 76.2 (250) 121.9 (400) 243.8 (800) 274.3 (900) 1321-3R160-C 50 375/750
132 2/4 24.4 (80) 45.7 (150) 76.2 (250) 121.9 (400) 243.8 (800) 274.3 (900) 1321-3R200-C 50 375/750
9
160 2 24.4 (80) 45.7 (150) 91.4 (300) 121.9 (400) 182.9 (600) 243.8 (800) 1321-3RB250-C 50 480
200 2 24.4 (80) 45.7 (150) 91.4 (300) 121.9 (400) 182.9 (600) 243.8 (800) 1321-3RB250-C 50 480
10
250 2 24.4 (80) 45.7 (150) 91.4 (300) 121.9 (400) 182.9 (600) 243.8 (800) 1321-3RB400-C 50 480
315 2 24.4 (80) 45.7 (150) 91.4 (300) 121.9 (400) 182.9 (600) 243.8 (800) 1321-3RB400-C 20 960
(3)
(3) Resistor specification is based on two parallel cables per phase.
355 2 24.4 (80) 45.7 (150) 91.4 (300) 121.9 (400) 182.9 (600) 243.8 (800) 1321-3R500-C 20 960
(3)
400 2 24.4 (80) 45.7 (150) 91.4 (300) 121.9 (400) 182.9 (600) 243.8 (800) 1321-3R500-C 20 960
(3)
11
450 2 24.4 (80) 45.7 (150) 91.4 (300) 121.9 (400) 182.9 (600) 243.8 (800) 1321-3R750-C 20 960
(3)
500 2 24.4 (80) 45.7 (150) 91.4 (300) 121.9 (400) 182.9 (600) 243.8 (800) 1321-3R750-C 20 960
(3)
560 2 24.4 (80) 45.7 (150) 76.2 (250) 121.9 (400) 182.9 (600) 243.8 (800) 1321-3R850-C 20 960
(3)
12
(1)
(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.
630 2 24.4 (80) 45.7 (150) 76.2 (250) 121.9 (400) 182.9 (600) 243.8 (800) 2 x 1321-3R600-C 40 480
(4)
(4) Resistor specification is based on three parallel cables per phase.
710 2 24.4 (80) 45.7 (150) 76.2 (250) 121.9 (400) 182.9 (600) 243.8 (800) 2 x 1321-3R600-C 40 645
(4)
800 2 24.4 (80) 45.7 (150) 76.2 (250) 121.9 (400) 182.9 (600) 243.8 (800) 2 x 1321-3R750-C 40 645
(4)
13
900 2 24.4 (80) 45.7 (150) 76.2 (250) 121.9 (400) 182.9 (600) 243.8 (800) 2 x 1321-3R600-C 40 645
(4)
1000
(2)
(2) Some Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.
2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 182.9 (600) 243.8 (800) 2 x 1321-3R600-C 20 840
(5)
(5) Resistor specification is based on four parallel cables per phase.
1100
(2)
2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 182.9 (600) 243.8 (800) 2 x 1321-3R750-C 20 840
(5)