Manual

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014 107
Motor Cable Length Restrictions Tables Appendix A
Table 44 - PowerFlex 700S Drives, 600V Shielded/Unshielded Cable – Meters (Feet)
Drive No Solution Reactor Only Reactor and Damping
Resistor or 1321-RWR
Reactor/RWR
(see page 129
)
Resistor Available Options
Frame Hp kHz 1488V 1850V 1488V 1850V 1488V 1850V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
1
1 2/4 24.4 (80) 121.9 (400) 24.4 (80) 182.9 (600) 182.9 (600) 182.9 (600)
●●
2 2/4 24.4 (80) 121.9 (400) 24.4 (80) 182.9 (600) 182.9 (600) 182.9 (600)
●●●●
3 2/4 24.4 (80) 121.9 (400) 24.4 (80) 182.9 (600) 182.9 (600) 182.9 (600)
●●●●
5 2/4 24.4 (80) 121.9 (400) 24.4 (80) 243.8 (800) 365.8 (1200) 365.8 (1200) 1321-RWR8-EP
●●●●
7.5 2/4 24.4 (80) 121.9 (400) 24.4 (80) 304.8 (1000) 365.8 (1200) 365.8 (1200) 1321-RWR8-EP
●●
10 2/4 24.4 (80) 121.9 (400) 24.4 (80) 365.8 (1200) 365.8 (1200) 365.8 (1200) 1321-RWR12-EP
●●
15 2/4 24.4 (80) 121.9 (400) 36.6 (120) 365.8 (1200) 365.8 (1200) 365.8 (1200) 1321-RWR18-EP
2
20 2/4 24.4 (80) 121.9 (400) 36.6 (120) 365.8 (1200) 365.8 (1200) 365.8 (1200) 1321-RWR25-EP
25 2/4 24.4 (80) 121.9 (400) 45.7 (150) 365.8 (1200) 365.8 (1200) 365.8 (1200) 1321-RWR25-EP
3
30 2/4 24.4 (80) 121.9 (400) 45.7 (150) 365.8 (1200) 365.8 (1200) 365.8 (1200) 1321-RWR35-EP
40 2/4 24.4 (80) 137.2 (450) 45.7 (150) 365.8 (1200) 304.8 (1000) 365.8 (1200) 1321-RWR45-EP
50 2/4 24.4 (80) 137.2 (450) 45.7 (150) 304.8 (1000) 304.8 (1000) 365.8 (1200) 1321-RWR55-EP
4 60 2/4 24.4 (80) 137.2 (450) 45.7 (150) 304.8 (1000) 304.8 (1000) 365.8 (1200) 1321-RWR80-EP
5
75 2/4 24.4 (80) 137.2 (450) 45.7 (150) 274.3 (900) 243.8 (800) 365.8 (1200) 1321-RWR80-EP
100 2/4 24.4 (80) 137.2 (450) 45.7 (150) 243.8 (800) 243.8 (800) 365.8 (1200) 1321-RWR100-EP
6
125 2/4 24.4 (80) 137.2 (450) 61.0 (200) 243.8 (800) 198.1 (650) 365.8 (1200) 1321-RWR130-EP
150 2/4 24.4 (80) 137.2 (450) 61.0 (200) 243.8 (800) 198.1 (650) 365.8 (1200) 1321-RWR160-EP
9
150 2 24.4 (80) 137.2 (450) 61.0 (200) 243.8 (800) 198.1 (650) 365.8 (1200) 1321-RWR200-EP
200 2 24.4 (80) 137.2 (450) 61.0 (200) 243.8 (800) 198.1 (650) 365.8 (1200) 1321-RWR250-EP
10
250 2 24.4 (80) 137.2 (450) 61.0 (200) 198.1 (650) 167.6 (550) 365.8 (1200) 1321-3RB250-B 50 315
350 2 24.4 (80) 91.4 (300) 61.0 (200) 152.4 (500) 167.6 (550) 365.8 (1200) 1321-3RB350-B 20 585
(3)
(3) Resistor specification is based on two parallel cables per phase.
400 2 24.4 (80) 91.4 (300) 61.0 (200) 152.4 (500) 167.6 (550) 365.8 (1200) 1321-3RB400-B 20 585
(3)
450 2 24.4 (80) 91.4 (300) 61.0 (200) 152.4 (500) 167.6 (550) 365.8 (1200) 1321-3R500-B 20 585
(3)
11
500 2 24.4 (80) 91.4 (300) 61.0 (200) 152.4 (500) 167.6 (550) 365.8 (1200) 1321-3R500-B 20 585
(3)
600 2 24.4 (80) 91.4 (300) 61.0 (200) 152.4 (500) 152.4 (500) 365.8 (1200) 1321-3R600-B 20 585
(3)
12
(1)
(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.
700 2 24.4 (80) 91.4 (300) 61.0 (200) 152.4 (500) 152.4 (500) 365.8 (1200) 2 x 1321-3RB320-B 40 300
(3)
800 2 24.4 (80) 91.4 (300) 61.0 (200) 152.4 (500) 152.4 (500) 365.8 (1200) 2 x 1321-3RB400-C 40 480
(4)
(4) Resistor specification is based on three parallel cables per phase.
900 2 24.4 (80) 91.4 (300) 61.0 (200) 152.4 (500) 152.4 (500) 365.8 (1200) 2 x 1321-3R400-B 40 480
(4)
13
(2)
(2) Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.
1000 2 24.4 (80) 91.4 (300) 61.0 (200) 152.4 (500) 152.4 (500) 365.8 (1200) 2 x 1321-3R500-C 20 480
(4)
1100 2 24.4 (80) 91.4 (300) 53.3 (175) 137.2 (450) 137.2 (450) 365.8 (1200) 2 x 1321-3R500-B 20 720
(5)
(5) Resistor specification is based on four parallel cables per phase.
1300 2 24.4 (80) 91.4 (300) 53.3 (175) 137.2 (450) 137.2 (450) 365.8 (1200) 2 x 1321-3R600-B 20 720
(5)