Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014 103
Motor Cable Length Restrictions Tables Appendix A
Table 40 - PowerFlex 700L Drives with 700S Control, 600V Input Shielded/Unshielded Cable – Meters (Feet)
Table 41 - PowerFlex 700L Drives with 700S Control, 690V Input Shielded/Unshielded Cable – Meters (Feet)
Drive No Solution Reactor Only Reactor and
Damping Resistor
Reactor Resistor Available Options
Frame Hp kHz 1488V 1850V 1488V 1850V 1488V 1850V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
3A 465
2
18.3
(60)
76.2
(250)
18.3
(60)
76.2
(250)
182.9
(600)
304.8
(1000)
1321-3R500-B
(1)
(1) Requires two parallel cables.
20 585
●
4
18.3
(60)
76.2
(250)
18.3
(60)
76.2
(250)
182.9
(600)
304.8
(1000)
1321-3R500-B
(1)
20 1170
3B 870
2
18.3
(60)
61.0
(200)
18.3
(60)
61.0
(200)
152.4
(500)
228.6
(750)
1321-3R850-B
(2)
(2) Requires three parallel cables.
20 960
4
18.3
(60)
61.0
(200)
18.3
(60)
61.0
(200)
152.4
(500)
228.6
(750)
1321-3R850-B
(2)
20 1920
3B 1275 2
12.2
(40)
45.7
(150)
12.2
(40)
45.7
(150)
121.9
(400)
228.6
(750)
2 x
1321-3R600-B
(3)
(3) Requires four parallel cables.
20 720
Drive No Solution Reactor Only Reactor and
Damping Resistor
Reactor Resistor Available Options
Frame kW kHz 1488V 1850V 1488V 1850V 1488V 1850V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
3A 355
2
24.4
(80)
45.7
(150)
24.4
(80)
45.7
(150)
228.6
(750)
304.8
(1000)
1321-3R500-C
(1)
(1) Requires two parallel cables.
20 960
●
4
24.4
(80)
45.7
(150)
24.4
(80)
45.7
(150)
182.9
(600)
228.6
(750)
1321-3R500-C
(1)
20 1920
3B 657
2
24.4
(80)
45.7
(150)
24.4
(80)
45.7
(150)
182.9
(600)
228.6
(750)
1321-3R850-C
(2)
(2) Requires three parallel cables.
20 1290
4
24.4
(80)
45.7
(150)
24.4
(80)
45.7
(150)
182.9
(600)
228.6
(750)
1321-3R850-C
(2)
20 2580
3B 980 2
24.4
(80)
45.7
(150)
24.4
(80)
45.7
(150)
182.9
(600)
228.6
(750)
2 x
1321-3R600-C
(3)
(3) Requires four parallel cables.
20 840