Appendix A Motor Cable Length Restrictions Tables
Table 32 - PowerFlex 700H Drives, 600V Shielded/Unshielded Cable – Meters (Feet)
Table 33 - PowerFlex 700H Drives, 690V Shielded/Unshielded Cable – Meters (Feet)
PowerFlex 700L
This section lists motor cable length restrictions, reactors, and available options
for PowerFlex 700L drives.
Drive No Solution Reactor Only Reactor and Damping Resistor
or 1321-RWR
Reactor/RWR
(see page 129
)
Resistor Available Options
Frame Hp kHz 1488V 1850V 1488V 1850V 1488V 1850V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
9
150 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 198.1 (650) 365.8 (1200) 1321-RWR200-EP
200 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 198.1 (600) 365.8 (1200) 1321-RWR250-EP
10
250 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 167.6 (550) 365.8 (1200) 1321-3RB250-B 50 315
350 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 167.6 (550) 365.8 (1200) 1321-3RB350-B 20 585
(3)
(3) Resistor specification is based on two parallel cables per phase.
400 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 167.6 (550) 365.8 (1200) 1321-3RB400-B 20 585
(3)
450 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 167.6 (550) 365.8 (1200) 1321-3R500-B 20 585
(3)
11
500 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 167.6 (550) 365.8 (1200) 1321-3R500-B 20 585
(3)
600 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 152.4 (500) 365.8 (1200) 1321-3R600-B 20 585
(3)
12
(1)
(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.
700 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 152.4 (500) 365.8 (1200) 2 x 1321-3RB320-B 40 300
(3)
800 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 152.4 (500) 365.8 (1200) 2 x 1321-3RB400-C 40 480
(4)
(4) Resistor specification is based on three parallel cables per phase.
900 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 152.4 (500) 365.8 (1200) 2 x 1321-3R400-B 40 480
(4)
13
(2)
(2) Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.
1000 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 152.4 (500) 365.8 (1200) 2 x 1321-3R500-C 20 480
(4)
1100 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 137.2 (450) 365.8 (1200) 2 x 1321-3R500-B 20 720
(5)
(5) Resistor specification is based on four parallel cables per phase.
1300 2 24.4 (80) 45.7 (150) 61.0 (200) 91.4 (300) 137.2 (450) 365.8 (1200) 2 x 1321-3R600-B 20 720
(5)
Drive No Solution Reactor Only Reactor and Damping Resistor Reactor Resistor Available Options
Frame kW kHz 1850V 2000V 1850V 2000V 1850V 2000V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
9
160 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 137.2 (450) 1321-3RB250-C 50 480
200 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 137.2 (450) 1321-3RB250-C 50 480
10
250 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 137.2 (450) 1321-3RB400-C 50 480
315 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 1321-3RB400-C 20 960
(3)
(3) Resistor specification is based on two parallel cables per phase.
355 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 1321-3R500-C 20 960
(3)
400 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 1321-3R500-C 20 960
(3)
11
450 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 1321-3R750-C 20 960
(3)
500 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 1321-3R750-C 20 960
(3)
560 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 1321-3R850-C 20 960
(3)
12
(1)
(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.
630 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 2 x1321-3R600-C 40 480
(4)
(4) Resistor specification is based on three parallel cables per phase.
710 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 2 x1321-3R600-C 40 645
(4)
800 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 2 x1321-3R750-C 40 645
(4)
13
900 2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 2 x1321-3R600-C 40 645
(4)
1000
(2)
(2) Some Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.
2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 2 x1321-3R600-C 20 840
(5)
(5) Resistor specification is based on four parallel cables per phase.
1100
(2)
2 7.6 (25) 30.5 (100) 7.6 (25) 30.5 (100) 121.9 (400) 152.4 (500) 2 x1321-3R750-C 20 840
(5)