Control Method
Induction Motor:
Brushless Motor:
Indirect Self–Organized, Field–Oriented Control,
Current–regulated, sine coded PWM with
programmable carrier frequency.
Indirect Self-Organized, Field-Oriented Control, Current-regulated. Sine coded PWM with programmable carrier frequency.
Ratings apply to all drives. Refer to the PowerFlex® 700S - Phase II Control Reference Manual, publication PFLEX-RM003, for
derating guidelines. The drive can be supplied as 6 pulse or 12 pulse in a configured package.
Carrier Frequency
HP Drive RatingCarrier Frequency
1–604 kHz 1–12 kHz
15-2502 kHz1-6 kHz
300–5002 kHz1-4 kHz
600–6501.5 kHz1-4 kHz
700–8001 kHz1-4 kHz
Drive rating: 4 kHz
Settings: 2, 4, 6, 8, 10 kHz
(6 kHz is for V/Hz operation only)
Drive rating: 2 kHz
Settings: 2, 4, 6, 8, 10 kHz
(6 kHz is for V/Hz operation only)
Output Voltage Range:
0 to rated motor voltage 0 to rated motor voltage
Output Frequency Range:
0 to 250 Hz. 0 – 400 Hz 0 – 400 Hz Note: For output frequencies above 320 - 400 Hz
consult the factory.
Speed Control
Speed Regulation – without encoder feedback
1% of top speed over a 40:1 speed range
Speed regulation - without feedback
0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth
Speed regulation - without feedback
0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth
Speed regulation - with encoder feedback
0.001% of top speed over a 100.1 speed range
Speed regulation - with feedback
0.001% of base speed across 120:1 speed range
1000:1 operating range
744 rad/sec bandwidth
Speed regulation - with feedback
0.001% of base speed across 120:1 speed range
1000:1 operating range
300 rad/sec bandwidth
Torque Regulation
Torque Regulation - without feedback
+/-5% of rated motor torque
Torque Regulation - without feedback
+/-5%, 600 rad/sec bandwidth
Torque Regulation - without feedback
+/-10%, 600 rad/sec bandwidth
—
Torque Regulation - with feedback
+/-2%, 2500 rad/sec bandwidth
Torque Regulation - with feedback
+/-5%, 2500 rad/sec bandwidth
Selectable Motor Control:
Field Oriented Control with and without a feedback
device.
Field Oriented Control with and without a feedback device and permanent magnet motor control
Stop Modes:
Multiple programmable stop modes including –
Ramp, Coast and Current Limit
Multiple programmable stop modes including – Ramp, Coast and Current Limit
Accel/Decel
Independently programmable accel and decel times
adjustable from 0 to 6553.5 in 0.1 second
increments.
Independently programmable accel and decel times adjustable from 0 to 6553.5 in 0.1 second increments.
S-Curve Time
— Adjustable from 0.5 to 4.0 seconds
Intermittent Overload:
150% for 1 minute
200% of motor rating for 10 secs - up to inverter limit
110% Overload capability for up to 1 minute
150% Overload capability for up to 3 seconds
Current Limit Capability:
Programmable from 200% of rated output current Independent Motoring and Regenerative Power Limits programmable to 800% of rated output current
Electronic Motor Overload
Protection
Programmable Motor Overload Protection (I
2
T)
investigated by UL to comply with NEC Article 430
Provides class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC
article 430.126 (A) (2). UL 508C File E59272.
Category
Specification
1336 FORCE Drive
PowerFlex 700S Phase II Drive Frames 1-6 (690V Drive
frames 5 & 6 only) PowerFlex 700S Phase II Drive Frames 9 & up