Manual

1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide
55
Environment Altitude: 1000 m (3300 ft) max. without derating. 1000 m (3300 ft.) max. without derating.
Surrounding Air Temp.
without Derating:
IP00, Open Type: 0 to 50° C (32 to 122° F) 0 to 50° C (32 to 122° F) Based on drive rating.
IP20, NEMA Type 1: 0 to 40° C (32 to 104° F) 0 to 40° C (32 to 104° F) Based on drive rating.
IP56, NEMA Type 4X:
0 to 40° C (32 to 104° F) Frames 9 & 10: 0 to 40 ° C (32 to 104 ° F) surrounding air.
IP65, NEMA Type 4 0 to 40° C (32 to 104° F)
Storage Temperature (all
const.):
–40 to 70° C (–40 to 158° F) -40 to 70° C (-40 to 158° F)
Relative Humidity:
5 to 95% non-condensing 5 to 95% non-condensing
Shock:
15G peak for 11ms duration (±1.0 ms) 10G peak for 11 ms duration (± 1.0 ms)
Vibration:
0.152 mm (0.006 in.) displacement, 1G peak 0.152 mm (0.006 in.) displacement, 1G peak, 5.5 Hz 2 mm (0.0787 in.) displacement, 1G peak EN50178 / EN60068-
2-6
Sound
—FrameFan
Speed
Sound
Level
Note: Sound pressure level is
measured at 2 meters.
Frame Sound
Level
Background
Noise Level
Notes: Sound pressure
level is measured at 1
meter. All devices
measured are 400V
IP21 and in power up
mode.
1 30 CFM 59 dB 9 78 49
2 50 CFM 57 dB 10 77 49
3 120 CFM 61 dB 13 76 46
4 190 CFM 59 dB
5 200 CFM 71 dB
6 300 CFM 72 dB
Atmosphere
Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust.
If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive
atmosphere.
Electrical AC Input
Voltage Tolerance:
±10% of minimum/maximum
See PowerFlex 700S Input Voltage Range/Tolerance
on page 59 for Full Power and Operating Range
Frequency Tolerance:
48-62 Hz. 47-63 Hz
Input Phases:
Three-phase input provides full rating for all drives.
Single-phase operation provides 50% of rated
current.
Three-phase input provides full rating for all drives. Single-phase operation provides 50% of rated current.
DC Input
Voltage Tolerance
±10% of Nominal Bus Voltage (above)
Displacement Power
Factor:
5.5-597 kW (7.5-800 HP): 0.95 0.98 across speed range
Efficiency:
97.5% at rated amps, nominal line volts. 97.5% at rated amps, nominal line volts.
Max. Short Circuit Current
Rating:
200,000 Amps, 600V, using recommended fuse or
circuit breaker type.
200,000 Amps, using recommended fuse or circuit breaker type.
Maximum Drive to Motor
Power Ratio
The drive to motor rating cannot exceed a 2:1 ratio
Category
Specification
1336 FORCE Drive
PowerFlex 700S Phase II Drive Frames 1-6 (690V Drive
frames 5 & 6 only) PowerFlex 700S Phase II Drive Frames 9 & up