Specifications
Category
Specification
1336 FORCE Drive
PowerFlex 700S Phase II Drive Frames 1-6 (690V Drive
frames 5 & 6 only) PowerFlex 700S Phase II Drive Frames 9 & up
Protection
Drive Voltage Class
380-480V 500-600V 200-208V 240V 380/400V 480V
600V
(frames
0-4)
600V /
690V
(frames
5&6) 380/400V 480V 500V 600V 690V
AC Input Overvoltage Trip:
570VAC 690VAC 300VAC 300VAC 600VAC 600VAC 863VAC 863VAC 675VAC 675VAC 675VAC 889VAC 889VAC
AC Input Undervoltage Trip: 280VAC 343VAC ——————— — — — —
Bus Overvoltage Trip:
810VDC 975VDC 405VDC 405VDC 810VDC 810VDC 1164VDC 1164VDC 911VDC 911VDC 911VDC 1200VDC 1200VDC
Bus Undervoltage Trip: 400VDC 498VDC Adjustable
Nominal Bus Voltage:
281VDC 324VDC 540VDC 648VDC 810VDC 931VDC 540VDC 648VDC 645VDC 810VDC 931VDC
All Frames
1336 FORCE Drive PowerFlex 700S Phase II Drive
Heat Sink Thermistor:
Monitored by microprocessor overtemp trip Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Current Limit:
Hardware Current Limit:
Instantaneous Curr.
Limit:
—
—
220% of rated output current
—
Calculated value, 105% of motor rated to 200% of drive rated
105% of 3 sec. rating (158%-210%)
143% of 3 sec rating (215%-287%)
Calculated value, 105% of motor rated to 200% of drive rated
360% of rated Heavy Duty current (typical)
—
Line Transients:
up to 6000 volts peak per IEEE C62.41-1991 Up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise
Immunity:
Showering arc transients up to 1500V peak Showering arc transients up to 1500V peak
Power Ride-Thru:
15 milliseconds at full load 15 milliseconds at full load
Logic Control Ride-Thru
0.5 second minimum, 2 seconds typical 0.25 sec., drive not running
Ground Fault Trip:
Phase-to-ground on drive output Phase-to-ground on drive output
Short Circuit Trip:
Phase-to-phase on drive output Phase-to-phase on drive output