1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide
29
PowerFlex 700S - Frame 11
No. Name Description
Wire Size Range
(1)
(2)
(1)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2)
Do Not exceed maximum wire size. Parallel connections may be required.
Torque
Terminal Bolt Size
(3)
(4)
(3)
These connections are bus bar type terminations and require the use of lug type connectors.
(4)
Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.
Maximum Minimum Recommended
1 Input Power Terminal Block
(4)
1L1, 1L2, 1L3, 2L1, 2L2, 2L3
AC Input power 300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N-m
(354 lb.-in.)
M12
2 Output Power Terminal Block
(4)
U/T1, V/T2, W/T3
Motor connections 300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N-m
(354 lb.-in.)
M12
3 SHLD Terminal, PE, Motor Ground
(4)
Terminating point for wiring shields 300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N-m
(354 lb.-in.)
M10
4 DC Bus
(4)
(2 Terminals; DC–, DC+)
DC input 300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N-m
(354 lb.-in.)
M12
5 Cable Clamp for Strain Relief
2L1
2L2
2L31L1
1L2
1L3
U/T1 V/T2 W/T3
DC-
DC+
3
1
2
4
5