PowerFlex 700S - Frames 5 & 6
No. Name Frame Description
Wire Size Range
(1)
(1)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
Torque Terminal
Bolt Size
(2)
(2)
Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.
Maximum Minimum Maximum Recommended
1 Power Terminal Block 5
(75 HP)
(3)
(3)
Not all terminals present on all drives.
R, S, T, BR1, 2, DC+, DC-, U, V and W 50.0 mm
2
(1/0 AWG)
2.5 mm
2
(14 AWG)
See Note
(4)
(4)
Refer to the terminal block label inside the drive.
See Note
(4)
—
PE 50.0 mm
2
(1/0 AWG)
4.0 mm
2
(12 AWG)
—
5
(100 HP)
(3)
R, S, T, DC+, DC-, U, V and W 70.0 mm
2
(2/0 AWG)
16.0 mm
2
(6 AWG)
—
BR1, BR2 50.0 mm
2
(1/0 AWG)
2.5 mm
2
(14 AWG)
—
PE 50.0 mm
2
(1/0 AWG)
4.0 mm
2
(12 AWG)
—
6 Input power and motor connections 120.0 mm
2
(4/0 AWG)
(5)
(5)
If necessary, two wires can be used in parallel to any of these terminals using two lugs.
2.5 mm
2
(14 AWG)
6 N-m
(52 lb.-in.)
6 N-m
(52 lb.-in.)
—
2 SHLD Terminal 5 & 6 Terminating point for wiring shields — — 1.6 N-m
(14 lb.-in.)
1.6 N-m
(14 lb.-in.)
—
3 AUX Terminal Block 5 & 6 Auxiliary Control Voltage
(6)
PS+, PS-
(6)
External control power: UL Installation - 300V DC, ±10%, Non UL Installation - 270-600V DC, ±10%. Frame 1-6, 100 W
4.0 mm
2
(10 AWG)
0.5 mm
2
(22 AWG)
0.6 N-m
(5.3 lb.-in.)
0.6 N-m
(5.3 lb.-in.)
—
4 Fan Terminal Block
(Common Bus Only)
5 & 6 User Supplied Fan Voltage
0V AC, 120V AC, 240V AC
4.0 mm
2
(10 AWG)
0.5 mm
2
(22 AWG)
0.6 N-m
(5.3 lb.-in.)
0.6 N-m
(5.3 lb.-in.)
—
WIRE RANGE: 14-1/0 AWG (2.5-35 MM
2
)
TORQU E: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY
POWER TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (16-35 MM
2
)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM
2
)
TORQU E: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
17
21
INPUT ACOUTPUT
Optional
Communications
Module
9
Frame 5
Frame 6
Optional
Communications
Module
L2L1T3T2T1 L3
INPUTOUTPUT
USE 75 C
COPPER WIRE
ONLY
TORQUE
52 IN-LB
(6 N-M)
BR2
PS+
PS–
BR1 DC+ DC–
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
3
2
1
2
3
1
4
4