Manual
1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide
13
c4
ND Rating
600V, 60Hz Input ♣
Code Amps Hp
1P7 1.7 1
2P7 2.7 2
3P9 3.9 3
6P1 6.1 5
9P0 9 7.5
011 11 10
017 17 15
022 22 20
027 27 25
032 32 30
041 41 40
052 52 50
062 62 60
077 77 75
099 99 100
125 125 125
144 144 150
170 170 150
208 208 200
261 261 250
325 325 350
385 385 400
416 416 450
460 460 450
502 502 500
590 590 600
650 650 700
750 750 800
820 820 900
920 920 1000
1K0 1030 1100
1K1 1180 1300
♣ Note: CE Certification testing has not been
performed on 600V class drives Frames 1…4.
c5
ND Rating
690V, 50 Hz Input ♣
Code Amps kW
052 52 45
060 60 55
082 82 75
098 98 90
119 119 110
142 142 132
170 170 160
208 208 200
261 261 250
325 325 315
385 385 355
416 416 400
460 460 450
502 502 500
590 590 560
650 650 630
750 750 710
820 820 800
920 920 900
1K0 1030 1000
1K1 1180 1100
♣ Note: CE Certification testing has not been
performed on 600V class drives Frames 1…4.
e
HIM
Code Operator Interface
0 Blank Cover
2 Digital LCD
3 Full Numeric LCD
5 Prog. Only LCD
C
Full Numeric LCD,
Door Mount
Frames 10 & up only.
f
Documentation
Code Documents
E Quick Start Guide
N No Documentation
g
Brake
Code w/Brake IGBT ‡
seYY
oNN
‡ Brake IGBT is standard on Frames 1-3 and
optional on Frames 4-9 ONLY.
h
Brake Resistor
Code w/Resistor
Y Yes
oNN
Not available for Frame 3 drives or larger.
j
Comm Slot
Code Version
N None
C DPI ControlNet (Coax)
D DPI DeviceNet
E DPI EtherNet/IP
R DPI RIO
S DPI RS-485 DF1
1 DriveLogix ControlNet (Coax)
2
DriveLogix ControlNet Redundant
(Coax)
3 DriveLogix ControlNet (Fiber)
4
DriveLogix ControlNet Redundant
(Fiber)
5 DriveLogix DeviceNet (Open Conn.)
6 DriveLogix EtherNet/IP
k
Control Options
Code
Control
Option
Logic
Expansion
Synch
-Link
Cassette
A
Phase
II
No No Expanded
B
Phase
II
No Yes Expanded
C
Phase
II
Yes No Expanded
D
Phase
II
Yes Yes Expanded
G
Phase
II
N/A No Slim
H
Phase
II
N/A Yes Slim
l
Feedback
Code Option
N
No Option
A
Resolver
B
Stegmann Hi-Resolution Encoder
C
Multi-Device Interface
E
2nd Encoder
S
Safe-Off (w/2nd Encoder)
Expanded cassette required.
One encoder interface is included with the
base drive.
m
Additional Config.
Code Description
E Phase II Control
K Phase II DriveLogix5730
L
Phase II DriveLogix5730
w/EtherNet/IP
This is an embedded EtherNet option that is
only available with DriveLogix5730.
i
Emission
Code
CE Filter ♣
CM Choke
A
Yes Yes
B
Yes No
N § No No
Frames 1-6 Only.
Frames 9 & up Only.
§ For use on a high resistive ground or
ungrounded distribution system (Frame 9 only).
♣ Note: CE Certification testing has not been
performed on 600V class drives Frames 1…4.
d
Enclosure
Code Enclosure
A IP20, NEMA Type 1
B §
IP21, NEMA Type 1,
MCC
N
Open/IP00
Frames 9 & up Only.
§ Frames 10-12 Only.