Manual

Chapter 5
Programming Parameters
5–60
CP Operating Options
[CP Options]
Parameter Number 227
Parameter Type Sink
Display Units Bits
Drive Units None
Factory Default 0000 0000 0000 0000
Minimum Value 0000 0000 0000 0000
Maximum Value 0000 0000 0011 0000
For proper operation, bits 0 to 6 must be
left at zero.
If bit 7 = 0, this allows the motor to coast to
a stop after the flux test is completed.
If bit 7 = 1, this brings the motor to a con-
trolled stop after the flux test is completed.
Parameter Number 228
Parameter Type Sink
Display Units x.x HP
Drive Units Display units x 10
Factory Default 30.0 HP
Minimum Value 1.0 HP
Maximum Value HP
Base Motor Speed
[Base Motor Speed]
Motor Nameplate Horsepower
[Base Motor HP]
Parameter Number 229
Parameter Type Sink
Display Units x RPM
Drive Units x
Factory Default 1,750 RPM
Minimum Value 1 RPM
Maximum Value 15,000 RPM
Motor Nameplate AMPS
[Base Motor Curr]
Parameter Number 230
Parameter Type Sink
Display Units x.x amps
Drive Units Display units x 10
Factory Default 0.2 amps
Minimum Value 0.1 amps
Maximum Value Based on parameter 220
Drive nameplate current rating of the
motor. Used for current reference scaling
and current processor feedback scaling.
User entered value of nameplate motor
horsepower. The drive uses this informa-
tion in the Dynamic Brake Resistor
temperature calculation.
User entered value of nameplate motor
speed in RPM. The drive uses this
information to convert motor velocity RPM
to/from drive per unit.
Motor Nameplate VOLTS
[Base Motor Volt]
Parameter Number 231
Parameter Type Sink
Display Units x Volt
Drive Units None
Factory Default 460 volt
Minimum Value 75 volt
Maximum Value 575 volt
Motor Nameplate Frequency
[Base Motor Freq]
Parameter Number 232
Parameter Type Sink
Display Units x.x Hz
Drive Units display units x 10
Factory Default 60 Hz
Minimum Value 1 Hz
Maximum Value 250 Hz
Drive nameplate voltage rating of the
motor.
Total number of motor poles in motor.
Motor Nameplate Poles
[Motor Poles]
Parameter Number 233
Parameter Type Sink
Display Units x poles
Drive Units None
Factory Default 4 poles
Minimum Value 2 poles
Maximum Value 40 poles
Motor Inertia
[Motor Inertia]
Parameter Number 234
Parameter Type Sink
Display Units x.xx Sec
Drive Units Display units x 100
Factory Default 0.60 Sec
Minimum Value 0.01 Sec
Maximum Value 655 Sec
Time taken to accelerate
an uncoupled motor from zero to base
speed at rated torque.
Drive nameplate frequency rating of the
motor.