Manual
Chapter 5
Programming Parameters
5–58
Perunit Motor Voltage
[Motor Volt Fdbk]
Displays the perunit value of motor voltage
as determined from an analog–to–digital
converter input. This data is scaled to read
1.0 pu at rated motor voltage. This is a
version of parameter 265 that has been
scaled to perunit to be compatible with
analog outputs. This data is averaged and
updated on a 50 millisecond basis.
Parameter Number 186
Parameter Type Source
Display Units x.x%
Drive Units 4096 = 100.0% motor voltage
Factory Default 0.0%
Minimum Value 0.0%
Maximum Value 800.0%
Rated Inverter Output Amps
[Base Drive Curr]
Parameter Number 220
Parameter Type Source
Display Units x.x amps
Drive Units Display units x 10
Factory Default 20.0 amps
Minimum Value 0.1 amps
Maximum Value 3,276.7 amps
Current rating of inverter.
Automatically set by drive at powerup as a
function of Power Structure Type. Used for
current ref scaling and current processor
feedback scaling.
Rated Inverter Input Voltage
[Base Line Volt]
Parameter Number 221
Parameter Type Source
Display Units x volt
Drive Units Non
Factory Default 460 volt
Minimum Value 75 volt
Maximum Value 575 volt
Drive Nameplate Voltage rating of inverter.
Automatically set by drive at powerup as a
function of Power Structure Type.
Inverter Carrier Frequency
[PWM Frequency]
Parameter Number 222
Parameter Type Sink
Display Units x Hz
Drive Units None
Factory Default 4,000 Hz
Minimum Value 1,000 Hz
Maximum Value 12,000 Hz
This parameter defines the drive carrier
frequency in Hz.