Manual

Chapter 5
Programming Parameters
5–44
CP Warning/None Configuration Select
[CP Warn Select]
Parameter Number 87
Parameter Type Sink
Display Units Bits
Drive Units None
Factory Default 0000 0000 0001 1111
Minimum Value 0000 0000 0000 0000
Maximum Value 1111 1111 1111 1111
Enums:
This word parameter determines conditions
detected by the Current Processor (CP)
that will be reported as either a drive fault
or drive warning condition. Each configu-
ration bit matches the bit definition of Pa-
rameter 82, 84 and 86. When a bit is set to
“1”, the corresponding condition in the
Drive will be reported as a FAULT, other-
wise the condition is reported as a
WARNING.
VP Fault/Warning Configuration Select
[VP Fault Select]
Parameter Number 88
Parameter Type Sink
Display Units Bits
Drive Units None
Factory Default 1111 1111 1111 1111
Minimum Value 0000 0000 0000 0000
Maximum Value 1111 1111 1111 1111
Enums:
This word parameter determines conditions
detected by the Velocity Processor (VP)
that will be reported as either a drive
FAULT or drive WARNING condition. Each
configuration bit matches the bit definitions
of Parameters 83, 85 and 89. When a bit
is set to “1” the corresponding condition in
the Drive will be reported as a FAULT,
otherwise the condition is reported as a
WARNING.
Bit Condition
0 Bus Ridethrough Timeout
1 Bus Precharge Timeout
2 Bus Drop (150 volts)
3 Bus Undervoltage
4 Bus Drop Cycles
5 Fast Flux Up Current < 50%
Bit Condition
0 Encoder Feedback Loss
1 Inverter Overemp Pending
2 Motor Overtemperature Tripped
3 Motor Overload Pending (I
2
T)
4 Motor Overload Trip (I
2
T)
5 Motor Stalled
6 External Fault
7 RMS Fault
8 Reserved, Leave Zero
Bit Condition
9 Parameter Limit
10 Math Limit
11 Dynamic brake overtemp
12 AC Motor Contactor Failure
13 Inverter Overload Pending (IT)
14 Drive to Drive Fault
15 Inverter Overload Trip (IT)
VP Warning/None Configuration Select
[VP Warn Select]
Parameter Number 89
Parameter Type Sink
Display Units Bits
Drive Units None
Factory Default 1111 1111 1111 1111
Minimum Value 0000 0000 0000 0000
Maximum Value 1111 1111 1111 1111
Enum:
This parameter determines conditions de-
tected by the Velocity Processor (VP) that
will be reported as either a drive FAULT or
WARNING or not reported (ignored). Each
configuration bit matches the bit definitions
of Parameters 83, 85 and 88. When a bit
is set to “1”, the corresponding condition in
the Drive will be reported as configured by
parameter 88. If the bit is set to “0”, the
condition is not reported.
Bit Condition
0 Encoder Feedback Loss
1 Inverter Overtemp Pending
2 Motor Overtemperature Tripped
3 Motor Overload Pending (I
2
T)
4 Motor Overload Trip (I
2
T)
5 Motor Stalled
6 External Fault
7 RMS Fault
Bit Condition
8 Not Used
9 Parameter Limit
10 Math Limit
11 Dynamic brake overtemp
12 AC Motor Contactor Failure
13 Inverter Overload Pending (IT)
14 Drive to Drive Fault
15 Inverter Overload Foldback (IT)