Owner's manual
5–21Programming
[Pulse/Enc Scale]
This parameter contains the scaling factor for both
pulse train inputs (TB2-7, 8) and encoder feedback
speed regulation (TB3 terminals 31-36).
1. Encoder Feedback Operation
Enter actual encoder pulses per revolution
2. Pulse Train Input
Scale
Factor
Incoming Pulse Rate (Hz)
Desired Command Freq.
Motor Poles
2
x=
Parameter Number 46
Parameter Type Read and Write
Display Units / Drive Units Factor / Pulses per Rev
Factory Default 1024 PPR (64 PPR frn<4.01)
Minimum Value 1
Maximum Value 4096
Pulse Train Example:
4 Pole Motor, 60 Hz = Max. Speed.
The 1336–MOD–N1 option outputs 64 Hz/Hz.
At full analog reference, the pulse output will
be 60 Hz x 64 Hz/Hz = 3840 pulses/sec.
Pulse/Enc Scale
3840 Hz
60 Hz
4 Poles
2
= 128
This value will create a command frequency of
60 Hz for full analog reference to the option.
=x
This group contains the necessary parameters to activate and program advanced features
of the drive.
Feature Select
[Dwell Frequency]
This value sets the frequency that the drive will
immediately output (no Accel Ramp) upon a start
command. This parameter requires a programmed
[Dwell Time].
Parameter Number 43
Parameter Type Read and Write
Display Units / Drive Units 0.1 Hertz / Hertz x 10
Factory Default 0.0 Hz
Minimum Value 0.0 Hz
Maximum Value 7.0 Hz
[Dwell Time]
This value sets the time the drive will continue to
output [Dwell Frequency] before ramping to [Freq
Command].
Parameter Number 44
Parameter Type Read and Write
Display Units / Units 1 Second / Seconds
Factory Default 0 Sec
Minimum Value 0 Sec
Maximum Value 10 Sec
Dwell Time
Frequency of
Applied Voltage
0
0
Time
Maximum
Dwell Frequency
Start
Command
Dwell
Time
Frequency Set