Owner's manual
5–53Programming
[Base Voltage]
This value should be set to the motor nameplate
rated voltage.
Parameter Number 18
Parameter Type Read and Write
Display Units / Drive Units 1 Volt / 4096 = Drive Rtd Volts
Factory Default Drive Rated Volts
Minimum Value 25% of Drive Rated Voltage
Maximum Value 120% of Drive Rated Voltage
[Base Frequency]
This value should be set to the motor nameplate
rated frequency.
Parameter Number 17
Parameter Type Read and Write
Display Units / Drive Units 1 Hertz / Hertz x 10 (x 1 frn<4.01)
Factory Default 60 Hz
Minimum Value 25 Hz
Maximum Value 400 Hz
Important: Please note the resolution change with Frn 4.01.
[Maximum Voltage]
This parameter sets the highest voltage the drive will
output.
Parameter Number 20
Parameter Type Read and Write
Display Units / Drive Units 1 Volt / 4096 = Drive Rtd Volts
Factory Default Drive Rated Volts
Minimum Value 25% of Drive Rated Voltage
Maximum Value 120% of Drive Rated Voltage
Motor Control