Owner's manual

547Programming
This group of parameters configures the Process PI Regulator.
Process PI
[Speed Control]
This parameter selects the type of speed modulation
active in the drive.
This parameter cannot be changed while the drive is
running.
Important: If encoder feedback closed loop speed
regulation is required, Encoder Fdbk must be
selected.
Parameter Number 77
Parameter Type Read and Write
Factory Default Slip Comp(No Control frn < 4.01)
Units Display Drive
No Control 0
Frequency regulation
Slip Comp 1 Slip compensation
Speed Droop 2 Negative slip compensation
PLL 3 Phase lock loop (requires frn < 4.01)
Encoder Fdbk 4 Encoder feedbackclosed loop
Droop + Reg 5 Enc. fdbk.closed loop w/ active droop
P Jump 6 Traverse function
Process PI 7 Closed loop PI control
[PI Config]
This parameter sets and displays the configuration
for the PI regulator.
Note: Reset Integrator (Int) is also available through
a digital input. See Input Mode Selection in Chapter
2.
Parameter Number 213
Parameter Type Read/Write
Factory Default 00000000
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Inv Error Changes sign of PI Error
Reset Int Holds KI at zero
Zero Clamp Prevents bidirectional operation
Sqrt Fdbk Uses square root of PI feedback value
Set Output 000011
Preload Int 001100
PI Enable 010101
Diagram 1 2 3
Spare
Diagram 1
Time
Enable
PI
Output
Command
Output
Freq.
Disable
02421 27 30181512963
Enable PI output integrates from zero drive ramps to
regulated frequency.
Disable PI output is forced to zero drive ramps to
unregulated frequency.
Enable PI output steps to preload and integrates from
there drive steps to preload and ramps from
there.
Disable PI output is forced to zero - drive ramps to
unregulated frequency.
Enable PI output integrates from preload drive
ramps from preload.
Disable PI output is held at preload - drive ramps to
unregulated speed (min. preload).
Note: Drive will step output equal to preload on start.
Diagram 2
Enable Disable
02421 27 301815
Preload
12963
Diagram 3
Enable Disable
02421 27 30181512963
Preload
Preload
Preload at Start
Preload at Start
Preload
Feed forward effect for
more dynamic response
Better response for
well defined systems
[PI Status]
This parameter displays the status of the Process PI
regulator.
Parameter Number 214
Parameter Type Read Only
Factory Default None
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Enabled
Spares