Owner's manual

545Programming
This group of parameters contains all the parameters necessary to activate encoder feed-
back for closed loop operation.
Encoder
Feedback
[Speed Control]
This parameter selects the type of speed modulation
active in the drive.
This parameter cannot be changed while the drive is
running.
Important: If encoder feedback closed loop speed
regulation is required, Encoder Fdbk must be
selected.
Parameter Number 77
Parameter Type Read and Write
Factory Default Slip Comp(No Control frn < 4.01)
Units Display Drive
No Control 0
Frequency regulation
Slip Comp 1 Slip compensation
Speed Droop 2 Negative slip compensation
PLL 3 Phase lock loop (requires frn < 4.01)
Encoder Fdbk 4 Encoder feedbackclosed loop
Droop + Reg 5 Enc. fdbk.closed loop w/ active droop
P Jump 6 Traverse function
Process PI 7 Closed loop PI control
[Encoder Type]
This parameter contains the feedback encoder signal
type. The drive can accept single-ended, single-
channel (Pulse) or differential (Quadrature) signals.
This cannot be changed while drive is running.
Parameter Number 152
Parameter Type Read and Write
Factory Default Pulse
Units Display Drive
Pulse 0
Quadrature 1
[Pulse/Enc Scale]
This parameter contains the scaling factor for both
pulse train inputs (TB2-7, 8) and encoder feedback
speed regulation (TB3 terminals 31-36).
1. Encoder Feedback Operation
Enter actual encoder pulses per revolution
2. Pulse Train Input
Scale
Factor
Incoming Pulse Rate (Hz)
Desired Command Freq.
Motor Poles
2
x=
Parameter Number 46
Parameter Type Read and Write
Display Units / Drive Units Factor / Pulses per Rev
Factory Default 1024 PPR (64 PPR frn<4.01)
Minimum Value 1
Maximum Value 4096
Pulse Train Example:
4 Pole Motor, 60 Hz = Max. Speed.
The 1336MODN1 option outputs 64 Hz/Hz.
At full analog reference, the pulse output will
be 60 Hz x 64 Hz/Hz = 3840 pulses/sec.
Pulse/Enc Scale
3840 Hz
60 Hz
4 Poles
2
= 128
This value will create a command frequency of
60 Hz for full analog reference to the option.
=x
[Maximum Speed]
This Parameter sets the output frequency at full
frequency reference for:
1. Encoder feedback speed regulation.
2. All analog inputs to TB2 (remote pot, 0-10V &
0-20 mA).
NOTE: [Maximum Freq.] must be raised to allow
operation or modulation above [Maximum Speed].
Parameter Number 151
Parameter Type Read and Write
Display Units / Drive Units 1 Hertz / Hertz x 10 (x 1 frn<4.01)
Factory Default 400 Hz
Minimum Value 0 Hz
Maximum Value 400 Hz
[Motor Poles]
This parameter contains the number of motor
magnetic poles. This value translates output
frequency into actual motor RPM during closed loop
operation. It is calculated from
[Motor NP Hertz] and [Motor NP RPM].
Parameter Number 153
Parameter Type Read Only
Display Units / Drive Units 1 Poles / Poles