Owner's manual

544 Programming
This group of parameters contains the parameters used to scale, in User Units, any drive
parameter for display on the HIM. Two scaled parameter values can be simultaneously
displayed when Process Mode is selected.
Process
Display
[Process 1 Par]
This parameter should be set to the number of the
parameter whose scaled value will be displayed on
Line 1 of the HIM Display Panel.
The maximum process value that can be displayed
is 99,999.99. If this value is exceeded, a character
string of asterisks (****) will appear on the display.
Parameter Number 127
Parameter Type Read and Write
Display Units / Drive Units Parameter # / Parameter #
Factory Default 1
[Process 1 Scale]
This value sets the scaling multiplier for
[Process 1 Par]. The displayed value will be:
[Process 1 Par] actual value
x [Process 1 Scale] value
Displayed Value
Parameter Number 128
Parameter Type Read and Write
Display Units / Drive Units Numeric / Scale x 100
Factory Default +1.00
Minimum Value 327.68
Maximum Value + 327.67
[Process 1 Txt 1-8]
Sets the User Units description for the value
determined by [Process 1 Par] and [Process 1 Scale].
This 8 character description will be shown on line 1 of
the display. Refer to the Character Map in Appendix A.
Parameter Number(s) 129-136
Parameter Type Read and Write
Display Units / Drive Units ASCII Code / ASCII Code
Factory Default Volts
[Process 2 Par]
This parameter should be set to the number of the
parameter whose scaled value will be displayed on
Line 2 of the HIM Display Panel.
The maximum process value that can be displayed
is 99,999.99. If this value is exceeded, a character
string of asterisks (****) will appear on the display.
Parameter Number 180
Parameter Type Read and Write
Display Units / Drive Units Parameter # / Parameter #
Factory Default 54
[Process 2 Scale]
This value sets the scaling multiplier for
[Process 2 Par]. The displayed value will be:
[Process 2 Par] actual value
x [Process 2 Scale] value
Displayed Value
Parameter Number 181
Parameter Type Read and Write
Display Units / Drive Units Numeric / Scale x 100
Factory Default +1.00
Minimum Value 327.68
Maximum Value + 327.67
[Process 2 Txt 1-8]
Sets the User Units description for the value
determined by [Process 2 Par] and [Process 2 Scale].
This 8 character description will be shown on line 2 of
the display. Refer to the Character Map in Appendix A.
Parameter Number(s) 182-189
Parameter Type Read and Write
Display Units / Drive Units ASCII Code / ASCII Code
Factory Default Amps