Owner's manual

539Programming
[Rated CT kW]
This parameter displays the rated CT kW of the
drive.
Parameter Number 149
Parameter Type Read Only
Display Units / Drive Units kW / kW x 100
Display Drive Rated Output kW
[Rated VT Amps]
This parameter displays the rated output current of
the drive.
Parameter Number 198
Parameter Type Read Only
Display Units / Drive Units 0.1 Amp / Amps x 10
Display Drive Rated Amps
[Rated VT kW]
This parameter displays the rated VT kW of the
drive.
Parameter Number 199
Parameter Type Read Only
Display Units / Drive Units kW / kW x 100
Display Drive Rated kW
This group of parameters contains binary masks for all control functions. The masks control
which adapters can issue control commands.
Masks
TB3
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6
Not Used
Each mask contains a bit for each adapter.
Individual bits can be set to Zero to lockout
control by an adapter or set to 1 to permit an
adapter to have control.
With drive software versions above 2.00 and a
Series A (version 3.0) or Series B HIM, a
Status description (bit ENUM) is displayed on
line 1.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Mask
[Direction Mask]
This parameter controls which adapters can issue
forward/reverse commands.
Parameter Number 94
Parameter Type Read and Write
Factory Default 01111110
Units Display Drive
0 0
Deny Control
1 1 Permit Control
[Start Mask]
This parameter controls which adapters can issue
start commands.
Parameter Number 95
Parameter Type Read and Write
Factory Default 01111111
Units Display Drive
0 0
Deny Control
1 1 Permit Control
[Jog Mask]
This parameter controls which adapters can issue
jog commands.
Parameter Number 96
Parameter Type Read and Write
Factory Default 01111111
Units Display Drive
0 0
Deny Control
1 1 Permit Control
Ratings