Owner's manual
5–39Programming
[Rated CT kW]
This parameter displays the rated CT kW of the
drive.
Parameter Number 149
Parameter Type Read Only
Display Units / Drive Units kW / kW x 100
Display Drive Rated Output kW
[Rated VT Amps]
This parameter displays the rated output current of
the drive.
Parameter Number 198
Parameter Type Read Only
Display Units / Drive Units 0.1 Amp / Amps x 10
Display Drive Rated Amps
[Rated VT kW]
This parameter displays the rated VT kW of the
drive.
Parameter Number 199
Parameter Type Read Only
Display Units / Drive Units kW / kW x 100
Display Drive Rated kW
This group of parameters contains binary masks for all control functions. The masks control
which adapters can issue control commands.
Masks
TB3
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6
Not Used
Each mask contains a bit for each adapter.
Individual bits can be set to “Zero” to lockout
control by an adapter or set to “1” to permit an
adapter to have control.
With drive software versions above 2.00 and a
Series A (version 3.0) or Series B HIM, a
Status description (bit ENUM) is displayed on
line 1.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Mask
[Direction Mask]
This parameter controls which adapters can issue
forward/reverse commands.
Parameter Number 94
Parameter Type Read and Write
Factory Default 01111110
Units Display Drive
“0” 0
Deny Control
“1” 1 Permit Control
[Start Mask]
This parameter controls which adapters can issue
start commands.
Parameter Number 95
Parameter Type Read and Write
Factory Default 01111111
Units Display Drive
“0” 0
Deny Control
“1” 1 Permit Control
[Jog Mask]
This parameter controls which adapters can issue
jog commands.
Parameter Number 96
Parameter Type Read and Write
Factory Default 01111111
Units Display Drive
“0” 0
Deny Control
“1” 1 Permit Control
Ratings