Owner's manual

533Programming
[Fault Alarms]
This parameter stores and displays
the last alarm conditions present
prior to a fault. Refer to Chapter 6
for further alarm information.
With drive software versions above
2.00 and a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number 173
Parameter Type Read Only
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor StalledGround Warning
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Mtr Overload
Unused
Bit 14
Hardware Current Limit
Motoring Current Limit
Motor OL Trip
Auto Reset
Voltage Check
Heatsink Temp
Auxiliary Input
4-20 mA Loss
[Flt Clear Mode]
This parameter controls the method for clearing
faults.
Parameter Number 39
Parameter Type Read and Write
Factory Default Enabled
Units Display Drive
Disabled 0
Faults cleared only by cycling power
Enabled 1 Faults cleared by issuing a valid
stop command (only through
TB3/HIM) or cycling power refer to
Bit 3 of the Logic Control Structure
on page A13
[Ground Warning]
Enables the Ground Warning fault when the drive
senses ground current in excess of 2 amperes
(approximate). Refer to Chapter 6 for further
information.
Parameter Number 204
Parameter Type Read and Write
Factory Default Disabled
Units Display Drive
Disabled 0
No Fault Generated
Enabled 1 Ground Warning Generated
Faults