532 Programming
[Flt Power Mode]
This parameter displays the power mode active at
the time of the last fault. These values can be
helpful in troubleshooting for a condition causing a
fault.
Parameter Number 144
Parameter Type Read Only
Factory Default None
Units Display Drive
1 1
Power up sequence in progress
2 2 Precharge in progress
3 3 Bus voltage being stored in memory
4 4 Ready for run cmnd. after power up
5 5 Power stage diagnostics running
6 6 Line loss detection occurred
7 7 Ready for run command after stop
8 8 Drive running
9 9 Motor flux decay delay
10 10 DC braking in progress
11 11 Drive fault occurred
12 12 Flying start search enabled
13 13 Deceleration in progress
14 14 SCR wake mode
15 15 SCR check mode
16 16 SCR wait mode
[Fault Frequency]
This parameter stores and displays the last
[Output Freq] prior to a fault.
Parameter Number 145
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq.
Factory Default None
Minimum Value 0.00 Hz
Maximum Value 400.00 Hz
[Flt Driv Status]
This parameter stores and displays
the last [Drive Status] prior to a
fault.
Bits 0-7 are displayed on lower half
of line 2 on HIM display, while, bits
8-15 are displayed on the upper half
of line 2.
With drive software versions above
2.00 and a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number 146
Parameter Type Read Only
Enabled
Running
Command Direction
Actual Direction
Accelerating
Decelerating
Faulted
At Speed
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Alarm
0 = Reverse
1 = Forward
0 = Reverse
1 = Forward
Reference
ID
Local
Adapter ID
Reference 15 14 13 12
Freq Select 1 0 0 0 0
Preset Freq 1 0 0 0 1
Preset Freq 2 0 0 1 0
Preset Freq 3 0 0 1 1
Preset Freq 4 0 1 0 0
Preset Freq 5 0 1 0 1
Preset Freq 6 0 1 1 0
Preset Freq 7 0 1 1 1
Freq Select 2 1 0 0 0
Adapter 1 1 0 0 1
Adapter 2 1 0 1 0
Adapter 3 1 0 1 1
Adapter 4 1 1 0 0
Adapter 5 1 1 0 1
Adapter 6 1 1 1 0
Jog Frequency 1 1 1 1
Local 11 10 9
TB3 0 0 0
1001
2010
3011
4100
5101
6110
Unused 1 1 1
Bit 14
Faults