Owner's manual

531Programming
[Blwn Fuse Flt]
Enabling this parameter will allow monitoring of the
bus fuse (in 30 kW/40 HP and up drives) and cause
a Blwn Fuse Flt.
Parameter Number 81
Parameter Type Read and Write
Factory Default Enabled
Units Display Drive
Disabled 0
No Fault Generated
Enabled 1 Blwn Fuse Flt Generated
[Low Bus Fault]
This parameter enables or disables the drive fault
condition for bus voltage below the Bus
Undervoltage Trip value listed in the Appendix.
Parameter Number 91
Parameter Type Read and Write
Factory Default Enabled
Units Display Drive
Disabled 0
No Fault Generated
Enabled 1 Undervolt Fault Generated
[Fault Data]Firmware 4.01 & later
This parameter displays fault related parameter
numbers or bit array information. Certain faults
generate additional information to aid fault
diagnosis.
Parameter Number 207
Parameter Type Read and Write
Display Units / Drive Units Parameter # / Parameter #
Factory Default None
Minimum Value 1
Maximum Value 255
[Flt Motor Mode]
This parameter displays the motor mode active at
the time of the last fault.
Parameter Number 143
Parameter Type Read Only
Factory Default None
Units Display Drive
1 1
Power up sequence in progress
2 2 Motor connected, drive off
3 3 DC boost being applied
4 4 Motor running at [Dwell Frequency]
5 5 Motor accelerating
6 6 Motor at command speed
7 7 Motor decelerating
8 8 Motor coasting
9 9 Motor under DC braking
10 10 Waiting for fault reset returns to 0
11 11 Start mode
12 12 Flying start search enable
13 13 Flying start w/encoder in process
Faults