Owner's manual

528 Programming
[Analog Out Sel]
This parameter selects the source that will drive the
analog output. This output is intended for metering
only and should not be used as process control
feedback.
Important: Firmware versions below 4.01 will have
fewer selections available.
Parameter Number 25
Parameter Type Read and Write
Factory Default Frequency
Units Display Drive
Frequency 0
Zero to programmed [Maximum Freq]
Current 1 Zero to 200%
Torque 2 Zero to 200%
Power 3 Zero to 200%
Voltage 4 Zero to 200%
% Motor OL 5 Zero to 200%
% Drive OL 6 Zero to 200%
Encoder 7 See [Pulse/Enc Hertz]
Speed Error 8 See [Speed Error]
PI Reference 9 See [PI Reference]
PI Feedback 10 See [PI Feedback]
PI Error 11 See [PI Error]
PI Output 12 See [PI Output]
[Anlg Out Offset]
This parameter enables the voltage or current offset
for the analog output TB2 terminals 4 & 9. This
internal value offsets 0-20mA to 4-20mA and
0-10V to 2-10V.
Parameter Number 154
Parameter Type Read and Write
Factory Default Disabled
Units Display Drive
Disabled 0
Enabled 1
Drive Output
Frequency
Maximum
Speed
Minimum
Frequency
0
V
0 mA
Offset
10 V
20 mA
Analog Output Signal
2
V
4 mA
Analog Out Offset
[Abs Analog Out]Firmware 4.01 & later
This parameter selects whether a signed value or
absolute value is used for analog out.
Parameter Number 233
Parameter Type Read and Write
Factory Default Enabled
Units Display Drive
Disabled 0
Enabled 1
[Set Anlg Out Lo]Firmware 4.01 & later
Sets the percentage of the [Analog Out Sel] value
that equals 0V/0 mA output.
Parameter Number 234
Parameter Type Read and Write
Display Units / Drive Units 0.1% /4096 = 100%
Factory Default 0.0%
Minimum Value 300.0%
Maximum Value +300.0%
[Set Anlg Out Hi]Firmware 4.01 & later
Sets the percentage of the [Analog Out Sel] value
that equals 10V/20 mA output.
Parameter Number 235
Parameter Type Read and Write
Display Units / Drive Units 0.1% /4096 = 100%
Factory Default 100.0%
Minimum Value 300.0%
Maximum Value +300.0%
I/O Config