5–28 Programming
[Analog Out Sel]
This parameter selects the source that will drive the
analog output. This output is intended for metering
only and should not be used as process control
feedback.
Important: Firmware versions below 4.01 will have
fewer selections available.
Parameter Number 25
Parameter Type Read and Write
Factory Default “Frequency”
Units Display Drive
“Frequency” 0
Zero to programmed [Maximum Freq]
“Current” 1 Zero to 200%
“Torque” 2 Zero to 200%
“Power” 3 Zero to 200%
“Voltage” 4 Zero to 200%
“% Motor OL” 5 Zero to 200%
“% Drive OL” 6 Zero to 200%
“Encoder” 7 See [Pulse/Enc Hertz]
“Speed Error” 8 See [Speed Error]
“PI Reference” 9 See [PI Reference]
“PI Feedback” 10 See [PI Feedback]
“PI Error” 11 See [PI Error]
“PI Output” 12 See [PI Output]
[Anlg Out Offset]
This parameter enables the voltage or current offset
for the analog output TB2 terminals 4 & 9. This
internal value offsets 0-20mA to 4-20mA and
0-10V to 2-10V.
Parameter Number 154
Parameter Type Read and Write
Factory Default “Disabled”
Units Display Drive
“Disabled” 0
“Enabled” 1
Drive Output
Frequency
Maximum
Speed
Minimum
Frequency
0
V
0 mA
Offset
10 V
20 mA
Analog Output Signal
2
V
4 mA
Analog Out Offset
[Abs Analog Out]–Firmware 4.01 & later
This parameter selects whether a signed value or
absolute value is used for analog out.
Parameter Number 233
Parameter Type Read and Write
Factory Default “Enabled”
Units Display Drive
“Disabled” 0
“Enabled” 1
[Set Anlg Out Lo]–Firmware 4.01 & later
Sets the percentage of the [Analog Out Sel] value
that equals 0V/0 mA output.
Parameter Number 234
Parameter Type Read and Write
Display Units / Drive Units 0.1% /4096 = 100%
Factory Default 0.0%
Minimum Value –300.0%
Maximum Value +300.0%
[Set Anlg Out Hi]–Firmware 4.01 & later
Sets the percentage of the [Analog Out Sel] value
that equals 10V/20 mA output.
Parameter Number 235
Parameter Type Read and Write
Display Units / Drive Units 0.1% /4096 = 100%
Factory Default 100.0%
Minimum Value –300.0%
Maximum Value +300.0%
I/O Config