Owner's manual

527Programming
[Dig Out Torque]
This value sets the trip point for the output contact at
TB2 terminals 10 & 11 when [Digital Out Sel] is set
to At Torque. The contact will be closed when
above this value.
Parameter Number 161
Parameter Type Read and Write
Display Units / Drive Units 0.1 Amps / 4096 = Rated Torque Amps
Factory Default 0.0 Amps
Minimum Value 0.0 Amps
Maximum Value 200% of [Rated Amps]
[Set 0-10 Vlt Lo] Firmware 4.01 & later
Sets the percentage of the 0-10 volt input that
represents [Minimum Freq].
Parameter Number 237
Parameter Type Read and Write
Display Units / Drive Units 0.1% /4096 = 100%
Factory Default 0.0%
Minimum Value 300.0%
Maximum Value +300.0%
[Set 0-10 Vlt Hi] Firmware 4.01 & later
Sets the percentage of the 0-10 volt input that
represents [Maximum Freq].
Parameter Number 238
Parameter Type Read and Write
Display Units / Drive Units 0.1% /4096 = 100%
Factory Default 100.0%
Minimum Value 300.0%
Maximum Value +300.0%
[Set 4-20 mA Lo] Firmware 4.01 & later
Sets the percentage of the 4-20 mA input that
represents [Minimum Freq].
Parameter Number 239
Parameter Type Read and Write
Display Units / Drive Units 0.1% /4096 = 100%
Factory Default 0.0%
Minimum Value 300.0%
Maximum Value +300.0%
[Set 4-20 mA Hi] Firmware 4.01 & later
Sets the percentage of the 4-20 mA input that
represents [Maximum Freq].
Parameter Number 240
Parameter Type Read and Write
Display Units / Drive Units 0.1% /4096 = 100%
Factory Default 100.0%
Minimum Value 300.0%
Maximum Value +300.0%
Input Volts
Output Hertz
Offset InvertNormal/Default
0
8
10
6
4
2
0
48
42
54 6036
302418126
Input Volts
Output Hertz
0
8
10
6
4
2
0
48
42
54 6036
302418126
Input Volts
Output Hertz
0
8
10
6
4
2
0
48
42
54 6036
302418126
Analog Input Configuration
Examples shown are for 0-10V. Settings for 4-20 mA are similar.
[Minimum Freq] = 0 Hz
[Maximum Freq] = 60 Hz
[Set 0-10 Vlt Lo] = 20%
[Set 0-10 Vlt Hi] = 100%
2-10 volt input signal provides 0-60 Hz output, resulting
in a 2 volt offset in the speed command.
[Minimum Freq] = 0 Hz
[Maximum Freq] = 60 Hz
[Set 0-10 Vlt Lo] = 100%
[Set 0-10 Vlt Hi] = 0%
Maximum input (100% of 10V=10V) represents a
minimum frequency of 0 Hz & minimum input (0% of
10V=0V) represents a maximum frequency of 60 Hz.
[Minimum Freq] = 0 Hz
[Maximum Freq] = 60 Hz
[Set 0-10 Vlt Lo] = 0%
[Set 0-10 Vlt Hi] = 100%
Minimum input (0% of 10V=0V) represents minimum
frequency of 0 Hz and maximum input (100% of
10V=10V) represents maximum frequency of 60 Hz.