Owner's manual
5–25Programming
[Traverse Period]
This value sets the time to complete one cycle of
speed modulation.
Parameter Number 78
Parameter Type Read and Write
Display Units / Drive Units 0.01 Second / Seconds x 100
Factory Default 0.00 Sec
Minimum Value 0.00 Sec
Maximum Value 30.00 Sec
[Max Traverse]
This value sets the peak amplitude of speed
modulation.
Parameter Number 79
Parameter Type Read and Write
Display Units / Drive Units 0.01 Hertz / 32767 = [Maximum Freq]
Factory Default 0.00 Hz
Minimum Value 0.00 Hz
Maximum Value 50% of [Maximum Freq]
Seconds
Hertz
Maximum Traverse (–)
Traverse
P-Jump
P-Jump (+)
P-Jump (–)
Output
Reference
Traverse Period
–20
0
10 20 30 40 50 60
20
40
Maximum Traverse (+)
Traverse Function
[P Jump]
This value sets the slip or inertia compensation
amplitude of speed modulation.
Parameter Number 80
Parameter Type Read and Write
Display Units / Drive Units 0.01 Hertz / 32767 = [Maximum Freq]
Factory Default 0.00 Hz
Minimum Value 0.00 Hz
Maximum Value 25% of [Maximum Freq]
Feature Select