Owner's manual
5–24 Programming
[Language]
This parameter selects between English and the
alternate language for the HIM display.
Parameter Number 47
Parameter Type Read and Write
Factory Default “English”
Units Display Drive
“English” 0
“Alternate” 1
[Speed Control]
This parameter is now located earlier in this group (effective with firmware version 4.01).
Refer to page 5–22 for parameter description.
[Flying Start En]
This value enables the flying start function and
chooses the method to be used. The drive will first
search from the direction it was last running.
Parameter Number 155
Parameter Type Read and Write
Factory Default Disabled
Units Display Drive
“Disabled” 0
“Speed Search” 1
Freq. sweep –see [FStart For./Rev.]
“Use Encoder” 2 Requires feedback encoder
“Track Volts” 3 Read back EMF from sync. p.m.
motor
ATTENTION: The “Speed Search” selection should not be
used with synchronous or permanent magnet motors. Motors
may be demagnetized during braking.
!
[FStart Forward]
This value sets the frequency at which the forward
speed search begins. If this value exceeds
[Maximum Freq], speed search will begin at
[Maximum Freq]. Forward search ends at zero Hertz
or when motor speed is found.
Parameter Number 156
Parameter Type Read and Write
Display Units / Drive Units 1 Hertz / Hertz
Factory Default 60 Hz
Minimum Value 0 Hz
Maximum Value 400 Hz
[FStart Reverse]
This value sets the frequency at which the reverse
speed search begins. If this value exceeds
[Maximum Freq], speed search will begin at
[Maximum Freq]. Reverse search ends at zero Hertz
or when motor speed is found.
Parameter Number 157
Parameter Type Read and Write
Display Units / Drive Units 1 Hertz / Hertz
Factory Default 0 Hz
Minimum Value 0 Hz
Maximum Value 400 Hz
[LLoss Restart] – Firmware 4.01 & later
This parameter selects the reconnect mode after
recovery from a line loss condition.
Parameter Number 228
Parameter Type Read and Write
Factory Default “Track Volts”
Units Display Drive
“Speed Search” 1
Frequency sweep
“Use Encoder” 2 Read feedback
“Track Volts” 3 Read motor volts
“Last Speed” 4 Start at last output
Feature Select