Owner's manual

522 Programming
[Speed Control]
This parameter selects the type of speed modulation
active in the drive.
This parameter cannot be changed while the drive is
running.
Important: If encoder feedback closed loop speed
regulation is required, Encoder Fdbk must be
selected.
Parameter Number 77
Parameter Type Read and Write
Factory Default Slip Comp(No Control frn < 4.01)
Units Display Drive
No Control 0
Frequency regulation
Slip Comp 1 Slip compensation
Speed Droop 2 Negative slip compensation
PLL 3 Phase lock loop (requires frn < 4.01)
Encoder Fdbk 4 Encoder feedbackclosed loop
Droop + Reg 5 Enc. fdbk.closed loop w/ active droop
P Jump 6 Traverse function
Process PI 7 Closed loop PI control
[Slip @ F.L.A.]
This value sets the amount of automatic increase or
decrease to the drive output to compensate for
motor slip. When [Speed Control] is set to Slip
Comp, a percentage of this value proportional to
output current is added to the drive output
frequency. When [Speed Control] is set to Droop, a
percentage of this value proportional to output
current is subtracted from the drive output
frequency.
Parameter Number 42
Parameter Type Read and Write
Display Units / Drive Units 0.1 Hertz / Hertz x 10
Factory Default 1.0 Hz (0.0 Hz frn < 4.01)
Minimum Value 0.0 Hz
Maximum Value 10.0 Hz (5.0 frn<4.01)
[Slip Comp Gain] Firmware 4.01 & later
This parameter is the gain for the slip compensation
and adjusts the recovery rate after a load change.
Parameter Number 195
Parameter Type Read and Write
Display Units / Drive Units None
Factory Default 1
Minimum Value 1
Maximum Value 40
[Run On Power Up]
This parameter enables the function that allows the
drive to automatically restart on Power Up. This
parameter requires that a two wire control scheme
be installed at TB3 and that a valid start contact be
present. Refer to Input Mode Selection figure in
Chapter 2.
Parameter Number 14
Parameter Type Read and Write
Factory Default Disabled
Units Display Drive
Disabled 0
Enabled 1
ATTENTION: This parameter may only be used as outlined in
NFPA79, paragraph 6-14 (exceptions 1-3) for specialized
applications. Equipment damage and/or personal injury may
result if this parameter is used in an inappropriate application.
!
[Reset/Run Tries]
This value sets the maximum number of times the
drive attempts to reset a fault and restart before the
drive issues a Max Retries Fault. See Chapter 6 for
a list of resettable faults.
Parameter Number 85
Parameter Type Read and Write
Display Units / Drive Units 1 Try / Tries
Factory Default 0
Minimum Value 0
Maximum Value 9
Feature Select