Instruction Manual
Troubleshooting 4–5
Troubleshooting
Fault & Code No.
Status
Indicates Action
Illegal Drv.
Type
F 34
On N/A N/A Flashing The power structure is not
supported.
1. Check that the Converter
Control Board and Gate Driver
Board are matched and
correspond to the Converter
frame size.
2. Reset and re-enable by:
a.Exiting to the EEProm Mode.
b. Resetting defaults.
c. Verifying that P1 is set to the
correct operating mode.
d.Resetting the Converter.
If the fault occurs again, replace
the Converter Control Board.
SW Malfunction
F 35
On N/A N/A Flashing Software error. Reset and re-enable the Converter.
If the fault occurs again, replace the
Converter Control Board.
Host/DSP Com Err
F 37
On N/A N/A Flashing Host processor unable to
communicate with the Converter
SCANport.
Reset and re-enable the Converter.
If the fault occurs again, replace the
Converter Control Board.
PwrUp DspCom Err
F 38
On N/A N/A Flashing Host processor unable to
communicate with the Converter
SCANport.
Reset and re-enable the Converter.
If the fault occurs again, replace the
Converter Control Board.
EE Checksum
F 39
On N/A N/A Flashing 1336 REGEN Converter parameter
database is corrupt.
Reinitialize Converter parameters
or:
1. Recall values.
2. Save values.
3. Reset and re-enable the
Converter.
If the fault occurs again, replace the
Converter Control Board.
Pwr Up Marker
F 40
On N/A N/A Flashing Fault queue text. N/A
Unknown Error
F 41
On N/A N/A Flashing Fault queue text. Reset and re-enable the Converter.
If the fault occurs again, replace the
Converter Control Board.
No Entry
F 42
On N/A N/A Flashing Fault queue text. N/A
Clear Faults
F 43
On N/A N/A Flashing Fault queue text. N/A
DS1
FAULT
DS2
ENABLE
DS3
STATUS
DS4
COM