Instruction Manual

Regenerative DC Bus Supply Operation 2–29
Programming
Parameter No. 1
Display Units bits
Parameter Type Read/Write
Factory Default XXXXX000
Regen Brake Mode
Min/Max Value
N/A
Drive Units 000 = 0
bin
Operational Mode
Sets the 1336 REGEN Line Regeneration Package mode of operation. The modes are defined
by the last (3) bits of a 16 bit word. To set the mode, first stop the 1336 REGEN Converter, set
the mode, then re-enable the converter.
Important: If the [Operational Mode] is reset while the 1336 REGEN Converter is enabled,
a System Mode Change Fault will occur. Issuing a reset command will clear the
fault and reset the converter.
Parameter No.
2
Display Units Amps
Parameter Type Read Only
Drive Units
1 = 0.1A
Rated AC Line Current
Displays the rated AC line current of the 1336 REGEN Converter.
Parameter No.
3
Display Units %
Min/Max Value -200/200
Parameter Type Read Only
Drive Units 100 = 4096
AC Line Current
Displays the actual I
q
AC line current in percent of rated AC line current. Positive values
indicate motoring Negative values indicate regeneration.
Parameter No.
4
Display Units %
Min/Max Value -200/200
Parameter Type Read Only
Drive Units 100 = 4096
Peak Load
Displays the peak motoring or regenerating current in percent of rated AC current. The peak
value is held for five seconds. Positive values indicate motoring Negative values indicate
regenerating.
ion
a
l
M
o
d
e
tper
a
O
00

1
0XXX
0
X
Bit 2 Bit 1 Bit 0
0 = Regen Brake Mode 1 = Regen DC Bus Supply Mode
0 = Fixed DC Bus Mode 1 = DC Bus Trim Mode
0 = 460VAC Input Line Voltage 1 = 380VAC Input Line Voltage
0 = Fixed DC Bus 1 = Scheduled DC Bus