Instruction Manual
Specifications B–3
Heat Dissipation
Altitude Derating
Communications Format
and Configuration
Logic Status Structure
This provides the drive status information that will be sent to the
logic controllers input image table when the communication
module is set to control converter.
Regenerative DC Bus Supply Operation Only — 380-480VAC Input
1336 REGEN
Package
Amp Rating Converter
Converter
Heatsink
Precharge
Unit
10%
Line
Reactor
Power
Line
Filter
Package
Total
48A 141W 820W 15W 186W 173W 1335W
78A 193W 1110W 29W 258W 236W 1826W
180A 522W 2664W 58W 474W 317W 4035W
Regenerative Brake Operation Only — 380-480VAC Input
1336 REGEN
Package
Amp Rating Converter
Converter
Heatsink
Precharge
Unit
3%
Line
Reactor
Package
Total
48A 141W 656W 15W 65W 877W
78A 193W 888W 29W 84W 1194W
180A 522W 2131W 58W 168W 2879W
m
(ft)
% of Rated Amps
100%
80%
90%
0 4,000
(13,200)
3,000
(9,900)
2,000
(6,600)
1,000
(3,300)
Altitude
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8
Ready
Enabled
Not Used
Faulted
Not Used