Instruction Manual
B–2 Specifications
Protection
AC Input Overvoltage Trip Factory Set to +15% of Nominal Line
Voltage
Heatsink Over Temperature Trip 100˚C
1336R Converter Overcurrent Trip
Software Overcurrent Limit Factory Set to 192% of AC Input Current
Hardware Overcurrent Limit Factory Set to 245% of AC Input Current
Line Transients
Up to 6000 Volts Peak per ANSI C62.41-1991
Control Logic Noise Immunity
Showering Arc Transients Up to 1500 Volts Peak
Power Ride-Thru
6 mSec. at Full Load
Control Logic Ride-Thru
0.5 Sec. Minimum, 2 Sec. Typical
Regenerative DC Bus Supply Mode
Only 380VAC Input 480VAC Input
Bus Overvoltage Trip 670VDC 850VDC
Bus Undervoltage Trip 430VDC 520VDC
Nominal Bus Voltage 610VDC 735VDC