Programming 6–15
Advanced Setup
[Motor Type]
This parameter should be set to match the type of motor
connected to the drive.
Parameter Number 41
Parameter Type Read and Write
Factory Default “Induction”
Units
Display Drive
“Induction 0 Requires no additional setting.
“Sync Reluc” 1 [Slip @ F.L.A.] & [DC Hold Level]
must be set to zero. [Stop Select 1 &
2] must be set to a selection other
than “DC Brake.
“Sync PM” 2 [Slip @ F.L.A.] & [DC Hold Level]
must be set to zero. [Stop Select 1 &
2] must be set to a selection other
than “DC Brake.
[Stop Select 2]
This parameter selects the stopping mode when the drive
receives a valid stop command unless
[Stop Select 1] is selected.
Parameter Number 52
Parameter Type Read and Write
Factory Default “Coast”
Units
Display Drive
“Coast” 0 Causes the drive to turn off
immediately.
“DC Brake” 1 Drive defluxes the motor and then
injects DC braking voltage into the
motor. Requires a value in both [DC
Hold Time] & [DC Hold Level].
“Ramp” 2 Drive decelerates to 0 Hz., then if [DC
Hold Time] & [DC Hold Level] are
greater than zero the holding brake
is applied. If the values equal zero,
then the drive turns off. Requires a
value in [Decel Time 1/2].
“S Curve” 3 Drive causes S Curve Ramp to 0 Hz
in [Decel Time 1/2] x 2.
“Ramp to Hold” 4 Drive decelerates to zero Hertz then
injects holding brake per [DC Hold
Level] (limited to 70% of drive rated
amps) until
a) a Start command is issued or
b) the Enable input is opened.
[KP Amps]
Sets the proportional gain for the current limiting function
of the drive. Default values are chosen for high inertia
loads. If faster accel is required, raising the gain will allow
additional current to the motor. Excess gain settings may
create unstable operation.
Parameter Number 193
Parameter Type Read and Write
Display Units / Drive Units NA / NA
Factory Default 100
Minimum Value 25
Maximum Value 400
[Speed Brake En]
Enabling this feature allows faster deceleration by raising
the flux in the motor and increasing the losses. Speed
change braking is used in sensorless vector mode only
and is effective for motors up to 20 HP.
Parameter Number 319
Parameter Type Read and Write
Factory Default “Disabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1 DC injection braking during decel
[Common Bus]
When enabled, internal precharge is disabled, allowing
common bus operation. “CB Precharge” must be selected
in [TB3 Term xx Sel].
Parameter Number 58
Parameter Type Read and Write
Factory Default “Disabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1