Metering
[Encoder Freq]
This parameter displays the frequency command present
at encoder input terminals of TB3. This value is displayed
whether or not this is the active frequency command.
Parameter Number 63
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq
Factory Default None
Minimum Value 400.00 Hz
Maximum Value +400.00 Hz
[Pulse Freq]
This parameter displays the frequency command present
at pulse input terminals of TB2. This value is displayed
whether or not this is the active frequency command.
Parameter Number 254
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq
Factory Default None
Minimum Value 400.00 Hz
Maximum Value +400.00 Hz
[MOP Freq]
This parameter displays the frequency command from the
MOP. The MOP frequency command can be adjusted by
TB3 (if present) and appropriate inputs are selected (see
page 2–27). Some SCANport adapters, including the RIO
Adapter, can also adjust the MOP frequency command.
This value is displayed whether or not this is the active
frequency command.
Parameter Number 137
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq
Factory Default None
Minimum Value 0.00 Hz
Maximum Value 400.00 Hz
[Heatsink Temp]
This parameter displays the heatsink temperature of the
drive.
Parameter Number 70
Parameter Type Read Only
Display Units / Drive Units 1° C / Deg. C
Factory Default None
Minimum Value 0
Maximum Value 255° C
[Power OL Count]
Displays the percentage of accumulated I
2
t for the drive
thermal overload protection. Running continuously above
115% of drive rated amps will accumulate a value of 100% and
generate a Power Overload Fault (F64).
Parameter Number 84
Parameter Type Read Only
Display Units / Drive Units 1 % / 4096 = 100%
Factory Default None
Minimum Value 0%
Maximum Value 200%
[Motor OL Count]
This parameter displays the percentage of accumulated
I
2
t for the motor overload protection. Running continuously at
programmed [Overload Amps] will accumulate approximately
70%. Reduction of load will reduce the OL count. 100% value
will generate an Overload Fault (F07).
Parameter Number 202
Parameter Type Read Only
Display Units / Drive Units 1 % / 4096 = 100%
Factory Default None
Minimum Value 0%
Maximum Value 200%
[Last Fault]
This parameter displays the last drive fault. It is updated
whenever a new fault occurs.
Parameter Number 4
Parameter Type Read Only
Display Units / Drive Units Fault Number / Fault Number
Factory Default None
Minimum Value None
Maximum Value None
Frequency
Displayed
Incoming Encoder Pulse Rate
[Encoder PPR]
=
Frequency
Displayed
Incoming Pulse Rate (Hz)
[Pulse Scale]
=