User Manual - Firmware 1.xxx-6.xxx Instruction Manual

Specifications and Supplemental Information A–7
Figure W
C200
Figure X
C250
Figure Y
CX300
Figure Z
CP350
CPR350
Figure AA
CP400
CPR400
Figure AB
C300-C600
Enclosed drive in
40° C. ambient
Figure AC
C300-C600
Enclosed drive in
41-50° C. ambient
Figure/Rating Derate Figure/Rating Derate
Carrier Frequency in kHz
2 4 6
50%
80%
90%
60%
40%
70%
100%
% of Drive
Rated Amps
Carrier Frequency in kHz
2 4 6
50%
80%
90%
60%
40%
70%
100%
% of Drive
Rated Amps
Carrier Frequency in kHz
2 4 6
50%
80%
90%
60%
40%
70%
100%
% of Drive
Rated Amps
% of Drive
Rated Amps
Carrier Frequency in kHz
2 4 6
60%
90%
70%
50%
80%
100%
% of Drive
Rated Amps
Carrier Frequency in kHz
2 4 6
60%
90%
70%
50%
80%
100%
Carrier Frequency in kHz
2 4 6
50%
80%
90%
60%
40%
70%
100%
% of Drive
Rated Amps
Assumes two (2) 725 CFM cooling fans for
IP 20 (NEMA Type 1) enclosure
C350
C300
C400
C450
C500
C600
Carrier Frequency in kHz
2 3 4
50%
80%
90%
60%
40%
70%
100%
% of Drive
Rated Amps
Assumes two (2) 725 CFM cooling fans for
IP 20 (NEMA Type 1) enclosure
C300/
C350
C400
C450
C500
C600
6kHZ Data Not Available at Time of Printing
Altitude and High Input Voltage
Figure/Rating Derate
Figure AD
Altitude - All
Ratings
Figure AE
High Input
Voltage
% of Drive
Rated Amps
Altitude
m
(ft)
100%
80%
90%
0 4,000
(13,200)
3,000
(9,900)
2,000
(6,600)
1,000
(3,300)
% of Drive
Rated Amps
Input Voltage
100%
80%
90%
240, 480 or 600V Nominal +6%+4%+2% +10%+8%
Required Only for the following drives:
1336F-x025 – 18.5 kW (25 HP) at 8 kHz
1336F-x030 – 22 kW (30 HP) at 6 or 8 kHz
1336F-x060 – 45 kW (60 HP) at 6 kHz
Standard Rating for Enclosed Drive in
40
°
C Ambient & Open Drive in 50
°
C Ambient.
Derating Factor for Enclosed Drive in
Ambient between 41
°
C & 50
°
C.