User Manual - Firmware 1.xxx-6.xxx Instruction Manual
Programming 6–49
Process
Display
This group of parameters contains the parameters used to scale, in “User Units”, any drive
parameter for display on the HIM. Two scaled parameter values can be simultaneously
displayed when Process Mode is selected.
[Process 1 Par]
This parameter should be set to the number of the param-
eter whose scaled value will be displayed on Line 1 of the
HIM Display Panel.
The maximum process value that can be displayed is
99,999.99. If this value is exceeded, a character string of
asterisks (****) will appear on the display.
Parameter Number 127
Parameter Type Read and Write
Display Units / Drive Units Parameter # / Parameter #
Factory Default 1
[Process 1 Scale]
This value sets the scaling multiplier for [Process 1 Par].
The displayed value will be:
Parameter Number 128
Parameter Type Read and Write
Display Units / Drive Units Numeric / Scale x 100
Factory Default +1.00
Minimum Value –327.68
Maximum Value +327.67
[Process 1 Txt 1-8]
Sets the “User Units” description for the value determined
by [Process 1 Par] and [Process 1 Scale]. This 8 character
description will be shown on line 1 of the display. Refer to
the Character Map in Appendix A.
Parameter Number(s) 129-136
Parameter Type Read and Write
Display Units / Drive Units ASCII Code / ASCII Code
Factory Default “Volts ”
[Process 2 Par]
This parameter should be set to the number of the param-
eter whose scaled value will be displayed on Line 2 of the
HIM Display Panel.
The maximum process value that can be displayed is
99,999.99. If this value is exceeded, a character string of
asterisks (****) will appear on the display.
Parameter Number 180
Parameter Type Read and Write
Display Units / Drive Units Parameter # / Parameter #
Factory Default 54
[Process 2 Scale]
This value sets the scaling multiplier for
[Process 2 Par]. The displayed value will be:
Parameter Number 181
Parameter Type Read and Write
Display Units / Drive Units Numeric / Scale x 100
Factory Default +1.00
Minimum Value –327.68
Maximum Value +327.67
[Process 2 Txt 1-8]
Sets the “User Units” description for the value determined
by [Process 2 Par] and [Process 2 Scale]. This 8 character
description will be shown on line 2 of the display. Refer to
the Character Map in Appendix A.
Parameter Number(s) 182-189
Parameter Type Read and Write
Display Units / Drive Units ASCII Code / ASCII Code
Factory Default “Amps ”
[Process 1 Par] actual value
x [Process 1 Scale] value
Displayed Value
[Process 2 Par] actual value
x [Process 2 Scale] value
Displayed Value